765-2704/200-000

Functions

22

Product manual | Version: 1.0.0
2AO FLD IOL CONV 0-10V

5.3 Process Image

Figure 6: Input and Output Process Data

5.3.1 Input Process Data

Table 33: Input Process Data

Byte

Data Type
(Bits)

Bit
Offset

Content

Value Range

Description

0

UIntegerT (4)

4

Device status

0

OK

1

Maintenance
required

2

Outside 
specification

3

Function test

4

Error

5.3.2 Output Process Data

Table 34: Output Process Data

Byte

Data
Type
(Bits)

Content

Value Range

Description

Factor

Offset

Unit

0

IntegerT
(16)

Current voltage value

Analog output 1

0 ... 11000

0 ... 11 VAC

0.001

0

V

2

IntegerT
(16)

Current voltage value

Analog output 2

0 ... 11000

0 ... 11 VAC

0.001

0

V

Summary of Contents for I/O SYSTEM FIELD 765-2704/200-000

Page 1: ...Product manual Version 1 0 0 WAGO I O SYSTEM FIELD 2 Channel Analog Output IO Link Converter 0 10 V 2 x M12 Con nector 765 2704 200 000...

Page 2: ...3 1 IO Link Side 13 4 3 2 Actuator Side 13 4 4 Dimensional Drawings 14 4 5 Circuit Diagram 15 4 6 Technical Data 16 5 Functions 17 5 1 Operating Modes 17 5 1 1 IO Link Mode 17 5 2 Parameter Descripti...

Page 3: ...1 Mounting the Product on a Mounting Clip 26 8 Connection 27 8 1 Connecting the Plug 27 9 Commissioning 28 9 1 Configuration and Parameterization 28 10 Transport and Storage 29 11 Diagnostics 30 11 1...

Page 4: ...use Non observance of the intended use Use without protective measures in an environment in which salt water salt spray mist icing corrosive fumes explosive gases direct sunlight and ionizing radiatio...

Page 5: ...may not be operated within the scope of the approval 1 2 Typographical Conventions Number Notation 100 Decimals Normal notation 0x64 Hexadecimals C notation 100 0110 0100 Binary In single quotation ma...

Page 6: ...nd source of hazard Possible consequences of hazard that also include severe injury Action step to reduce risk CAUTION Type and source of hazard Possible consequences of hazard that include at least s...

Page 7: ...einafter The trademarks are listed in the Appendix 8 Protected Rights 37 Subject to Change The instructions guidelines standards etc in this manual correspond to state of the art at the time the docum...

Page 8: ...ELV for all voltages with a nomi nal value of 24 VDC Connecting impermissible current or frequency values may destroy the product Grounding Protection Fuses When handling the product please ensure tha...

Page 9: ...0 Safety Product manual Version 1 0 0 9 2AO FLD IOL CONV 0 10V 2 5 Thermal Safety Observe permissible temperature range of connecting cables The conductor cross sections must be designed for the maxim...

Page 10: ...ffective interference immune acquisition and output of analog signals Digital communication can easily be introduced retrofitted when old systems are modernized The converter can be configured via IO...

Page 11: ...s Product manual Version 1 0 0 11 2AO FLD IOL CONV 0 10V 4 Properties 4 1 View Figure 1 View Table 1 Legend for Figure View No Custom Name 1 M12 A plug 8 IO Link Side 13 2 LEDs 8 Indicators 12 3 M12 A...

Page 12: ...000 Properties 12 Product manual Version 1 0 0 2AO FLD IOL CONV 0 10V 4 2 Indicators Figure 2 Indicators LEDs Table 2 Legend for Figure Indicators LEDs No LED Color 1 I OUT1 Yellow 2 POWER Green 3 II...

Page 13: ...M12 A socket 8 Actuator Side 13 4 3 1 IO Link Side Table 4 IO Link Side M12 A Plug Connection Pin Signal Description M12 A plug 4 pole 1 1L 24 VDC supply 2 Not assigned 3 1L 0 V power supply 4 C Q IO...

Page 14: ...765 2704 200 000 Properties 14 Product manual Version 1 0 0 2AO FLD IOL CONV 0 10V 4 4 Dimensional Drawings Figure 4 Dimensional Drawings...

Page 15: ...765 2704 200 000 Properties Product manual Version 1 0 0 15 2AO FLD IOL CONV 0 10V 4 5 Circuit Diagram Figure 5 Circuit Diagram...

Page 16: ...ines and Standards 35 Table 6 Technical Data Communication Name Value Manufacturer ID 285 0x011D Bytes 01 29 0x01 0x1D Product ID 8391312 0x800A90 Bytes 128 10 144 0x80 0x0A 0x90 Manufacturer WAGO Gmb...

Page 17: ...ODD Input Output Device Description required for configuration can be down loaded from the IO Link community s website www io link com 5 2 Parameter Description Parameters are set through the ISDU mec...

Page 18: ...ccess rights Read write Table 10 Variables Device Access Name Description Subindex Data Type Length Factory Setting Value Range Device access blocks 0 RecordT 16 bits Data manage ment bitOffs 1 Boolea...

Page 19: ...ingT Max 6 bytes 765 2704 0200 0000 5 2 6 Product ID Table 17 Variables Product ID General Index 19 Access rights Read only Table 18 Variables Product ID Name Description Subindex Data Type Length Fac...

Page 20: ...dex Data Type Length Factory Setting Value Range Hardware ver sion Unique manu facturer spe cific identifier of the hardware version of the individual prod uct 0 StringT 2 bytes 5 2 10 Firmware Versio...

Page 21: ...ables Function Tag General Index 25 Access rights Read write Table 30 Variables Function Tag Name Description Subindex Data Type Length Factory Setting Value Range Function Tag Option for tag ging the...

Page 22: ...Content Value Range Description 0 UIntegerT 4 4 Device status 0 OK 1 Maintenance required 2 Outside specification 3 Function test 4 Error 5 3 2 Output Process Data Table 34 Output Process Data Byte D...

Page 23: ...765 2704 200 000 Functions Product manual Version 1 0 0 23 2AO FLD IOL CONV 0 10V 5 3 3 Process Image Representation of the Voltage Value on the Output Figure 7 Analog Value Representation...

Page 24: ...0 s at max 6 25 A fire protection Alternatively the product can be powered by a limited energy circuit per IEC 61010 1 or Class 2 per UL 1310 CAUTION The input current is unrestricted no fire protecti...

Page 25: ...Remote parameterization Read and change parameter setting 4 IO Link master 5 Feldbus Profinet EtherCAT EtherNet IP etc 6 PLC 6 2 Behavior in the Event of a Communication Interruption In case of commun...

Page 26: ...moval 7 1 Mounting 7 1 1 Mounting the Product on a Mounting Clip The product can be secured with a Mounting Clip Figure 9 Mounting Clip Secured with an M4 Screw or Cable Tie Figure 10 Mounting Clip wi...

Page 27: ...protected by the use of a fuse or powered by a limited energy cir cuit 1 Connect the pluggable connectors of the connecting cables to the product 2 Tighten the cap nut with a tightening torque of at...

Page 28: ...meter channel You can find the individual parameters and additional information in 8 Parameter De scription 17 9 1 Configuration and Parameterization Note The product is in operating mode during param...

Page 29: ...optimal protection during transport and storage Store the product in suitable packaging preferably the original packaging Only transport the product in suitable containers packaging Make sure the prod...

Page 30: ...oltage II On The analog value is in the normal range 0 100 0 10 V Flashing 2 Hz The analog value is in the range 100 110 10 11 V Flashing 5 Hz There is a short circuit or overload at the output 11 2 D...

Page 31: ...st Event 2 Product status 1 Mainte nance required bitOffset 31 BooleanT 1 bit 0 0 noEv 1 0x8DFF Bit_30 Test Event 1 Product status 1 Mainte nance required bitOffset 30 BooleanT 1 bit 0 0 noEv 1 0x8DFE...

Page 32: ...lue outside valid range The parameter value that was written is outside the permissible value range 32819 d 0x8033 Parameter length overrun The length of the parameter that was written is greater than...

Page 33: ...ocess value uncertain Note This event is not transferred on the event channel It can only be read out via in dex 37 detailed diagnostics or 545 Bit Coded_ActiveEvents 36350 d 0x8DFE 1 Maintenance requ...

Page 34: ...d packaging Clear any data stored on electrical and electronic equipment Remove lithium ion batteries lead acid batteries or memory cards that are added to the electrical and electronic equipment Wear...

Page 35: ...V 0 10V 13 Appendix 13 1 Technical Data Approvals Guidelines and Standards See also 2 Data_sheet_765 2704 200 000 36 Note Subject to changes Please also observe the further product documentation You c...

Page 36: ...L listed Pending IO Link MTTF 373 years 2 Channel Analog Output IO Link Converter 0 10 V 2 x M12 Connector Application Decentralized preprocessing and output of analog signals This device controls a c...

Page 37: ...ple Inc registered in the USA and other countries App Store is a service mark of Apple Inc AS Interface is a registered trademark of the AS International Association e V BACnet is a registered tradema...

Page 38: ...PROFIBUS is a registered trademark of the PROFIBUS Nutzerorganisation e V PNO PROFINET is a registered trademark of the PROFIBUS Nutzerorganisation e V PNO QR Code is a registered trademark of DENSO W...

Page 39: ...LEDs 12 Figure 3 Connections 13 Figure 4 Dimensional Drawings 14 Figure 5 Circuit Diagram 15 Figure 6 Input and Output Process Data 22 Figure 7 Analog Value Representation 23 Figure 8 Connection Exam...

Page 40: ...Table 16 Variables Product Name 19 Table 17 Variables Product ID General 19 Table 18 Variables Product ID 19 Table 19 Variables Product Text General 19 Table 20 Variables Product Text 19 Table 21 Var...

Page 41: ...Diagnostics 30 Table 40 Variables Detailed Diagnostics General 30 Table 41 Variables Detailed Diagnostics 31 Table 42 Variables Active Events General 31 Table 43 Variables Active Events 31 Table 44 V...

Page 42: ...gs videos and other WAGO media are subject to copyright Distri bution or modification of the contents of these pages and videos is prohibited Furthermore the content may neither be copied nor made ava...

Reviews: