56
Connect Devices
WAGO-I/O-SYSTEM 750
750-493 3-Phase Power Measurement Module
Manual
Version 1.2.0
Pos: 84 /All e Seri en (Allgemei ne Module)/Ü berschriften für alle Serien/__ noch nicht ei nsortierte Ü berschriften müssen noch einsorti ert werden __/Leistungsmessung - Ü berschrift 2 @ 13\mod_1346327054898_21.docx @ 102149 @ 2 @ 1
7.4
Power Measurement
Pos: 85 /Serie 750 ( WAGO-I/O-SYST EM)/Anschli eßen/Anschl ussbeispi ele/Anal ogei ngangskl emmen/Leistungsmessung 750-0493 @ 24\mod_1443094930995_21.docx @ 192428 @ 33 @ 1
7.4.1
Power Measurement on a Machine
For measuring power, all of the eight CAGE CLAMPS
®
have to be connected
according to the figure below.
Do not confuse current and voltage clamps!
When making the connections do not confuse the current and voltage paths, as
connecting the phase voltages directly to the low impedance current clamps IL1
… IL3 shall destroy the I/O module!
Figure 14: Power Measurement on a Machine
Negative power values!
If you measure negative power values, check the connection of the associated
current transformer circuit in the proper direction.
7.4.2
Pos: 86 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1