EPSITRON®
Device Description
13
787-1668 Electronic Circuit Breaker
Manual
Version 1.1.0
Pos : 17 /All e Seri en (Allgemei ne Module)/Ü berschrif ten f ür alle Serien/G erätebesc hreibung/G erätebeschr eibung - Übersc hrift 1 @ 3\ mod_1233756084656_21. doc x @ 27096 @ 1 @ 1
3
Device Description
Pos : 18.1 /Serie 787 (EPSITRON)/ Ger ät ebesc hrei bung/ Bes chr eibung/ Anwendung/Anwendung 787-1668 @ 12\ mod_1342431638280_21. doc x @ 100295 @ @ 1
The 787-1668 electronic circuit breaker reliably protects up to 8 load circuits
against short circuiting and overloading. The 24 VDC input voltage is distributed
among 8 output channels, each of which can be provided with separate fuse
protection.
Table 4: Fuse Protection of Output Channels
Variant
Fuse protection for each output
channel (can be set)
787-1668
2 A, 3 A, 4 A, 6 A, 8 A, 10 A
787-1668/0106-0000
1 A, 2 A, 3 A, 4 A, 5 A, 6 A
787-1668/0006-1000
0,5 A, 1 A, 2 A, 3 A, 4 A, 6 A
(with active current limitation)
The electronics can accommodate brief current peaks.
Pos : 18.2 /Serie 787 (EPSITRON)/ Ger ät ebesc hrei bung/ Bes chr eibung/ Funkti on/Funktion 787-1668: Drehsc hal ter @ 12\ mod_1342432084601_21. doc x @ 100304 @ @ 1
There are 8 rotary switches on the device which can be used to set the nominal
current for each of the individual output channels.
Pos : 18.3 /Serie 787 (EPSITRON)/ Ger ät ebesc hrei bung/ Bes chr eibung/ LED-Anzeig e/LED-Anz eige 787- 16xx @ 12\ mod_1342431879376_21.doc x @ 100301 @ @ 1
The current status of the output channel is indicated by a multi-colored LED.
Pos : 18.4 /Serie 787 (EPSITRON)/ Ger ät ebesc hrei bung/ Bes chr eibung/ Funkti on/Funktion 787-16xx: Kurzsc hluss und Ü berlast @ 13\ mod_1342432174185_21. doc x @ 100307 @ @ 1
In the event of a short circuit or overloading, the individual output channel is de-
energized after a defined trip time.
Pos : 18.5 /Serie 787 (EPSITRON)/ Ger ät ebesc hrei bung/ Bes chr eibung/ Anwendung/Hinweis e/Hinweis: Ther misc he Ents pannung abwart en 787- 16xx @ 12\mod_1342431732847_21.doc x @ 100298 @ @ 1
Wait for temperature to return to normal!
If an output channel has been de-activated due to short-circuiting or overloading,
wait until the temperature returns to its normal range (cooling period) before re-
activating the channel.
Pos : 18.6 /Serie 787 (EPSITRON)/ Ger ät ebesc hrei bung/ Bes chr eibung/ Funkti on/Funktion 787-16xx: Sig nal kontakt e @ 13\ mod_1342433022224_21.doc x @ 100310 @ @ 1
The device contains control and signaling contacts, which can be used for reading
out information relevant to operation. These contacts are also used to activate and
de-activate specific output channels individually. This device is equipped with
•
one digital control input and
•
two digital signal outputs.
Pos : 19 /D okument ation allgemei n/ Glieder ungs elemente/---Seit enwechs el--- @ 3\ mod_1221108045078_0. doc x @ 21810 @ @ 1