EPSITRON®
Device Description
23
787-1668 Electronic Circuit Breaker
Manual
Version 1.1.0
3.5.4
Technical Data for "Ambient conditions"
Table 15: Technical data - "Ambient conditions"
Ambient temperature range
-25 °C … +70 °C
Derating
787-1668:
787-1668/0106-0000,
787-1668/0006-1000:
Maximum 10 A per output channel
Total output current
(all output channels)
50 A ≥ 60 °C,
40 A = 70 °C.
no derating
Requisite minimum spacing
(top/bottom)
40 mm
Requisite minimum spacing
(lateral)
0 mm
3.5.5
Technical Data for "Signaling"
Table 16: Technical data - "Signaling"
LED
green/red/orange (per output channel)
Control Input S1
non electrically isolated 24 VDC input
(relative to the module 0 V input)
Voltage level "active high":
minimum 15 V, maximum 30 V
Voltage level "active low":
minimum 0 V, maximum 5 V
Jitter for pulse pattern: ±5 % or ±5 ms;
with the higher value applying.
Waiting period after pulse sequence
(low level): minimum 200 ms
Signal Output S2
24 VDC, active high, short-circuit proof
maximum current carrying capacity:
25 mA
Signal Output S3
24 VDC, active high, short-circuit proof
maximum current carrying capacity:
25 mA
Control and Signaling Terminals
(S1, S2, S3)
WAGO-
MULTI CONNECTION
SYSTEM (MCS)
, 721 Series
Connection: 0.08 mm² … 2.5 mm²
(maximum 1.5 mm² with insulated
ferrule)
Pos : 34 /D okument ation allgemei n/ Glieder ungs elemente/---Seit enwechs el--- @ 3\ mod_1221108045078_0. doc x @ 21810 @ @ 1