Connecting Data and Supply Cables 

WAGO-SPEEDWAY 767 

 

 

767-4801/000-800 8DO 24V DC 0.5A IF (8xM8) 

 

Manual 

 

Version 1.1.0  

 

Do not use drop lines under any circumstances. This can lead to amplified 

line reflections and signal distortions, which greatly impair the transmission 

quality. 

Pos:  23.9 /Serie 767 (WAGO-SPEED WAY)/Anschl uss D aten- und Versorgungskabel/I/O-Modul e/Anschl uss_Hinweise  T eil 3.1 @ 8\mod_1278314911479_21.docx @  58959 @  @ 1 

 

 

Observe the exact positioning (coding) between plug and socket. 

 

Keep all cables a sufficient distance away from electromagnetic sources of 

interference in order to maintain a high level of interference resistance of 

the 767 system against electromagnetic emissions. 

 

Observe the minimum bending radiuses of the WAGO system cable. For 

more information, see the technical data at www.wago.com. 

 

When laying all cable, ensure that you do not lay it in shear areas of moving 

machine parts. 

 

Observe the correct layout of the potential equalization. 

Pos: 23.10 /Serie 767 ( WAGO-SPEED WAY)/Anschluss D aten- und Versorgungskabel/I/O-M odule/Anschluss_Z ubehör  allgemein @ 5\mod_1249287357968_21.docx @  39869 @ 2 @  1 

 

5.2 

Required Accessories 

The WAGO accessories listed below are required for connecting the data and 

supply cable. The associated item numbers can also be found in the fieldbus 

manuals for 767 Series, in the "Accessories" section. Select the manual 

appropriate to the 767 Series fieldbus you are using. 

 

S-BUS M12 terminator, IP 67 

 

S-BUS and supply cables, pre-assembled on both ends, IP 67 

 

Torque wrench 

 

Protective caps 

Pos: 23.11 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx  @  21810 @   @ 1 

 

 

 

Summary of Contents for 767-4801/000-800

Page 1: ...docx 64941 1 WAGO SPEEDWAY 767 Manual 767 4801 000 800 8DO 24V DC 0 5A IF 8xM8 Digital Output Module 24 V DC 0 5 A Version 1 1 0 Pos 3 Alle Serien Allgemeine M odul e Hinweise zur Dokumentation Impre...

Page 2: ...9 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we alway...

Page 3: ...Marking Possibilities and Fastening 16 3 3 Display Elements 17 3 4 Labeling 18 3 5 Schematic Diagram 20 3 6 Dimensions 21 3 7 Technical Data 22 3 7 1 General Information 22 3 7 2 Supply 22 3 7 3 Commu...

Page 4: ...ata 58 8 2 Input Data 60 9 Diagnostics 62 9 1 LED Signaling 62 10 Service 65 10 1 Updating the Firmware 65 10 2 Replacing the Module 65 10 2 1 Disconnecting the Cables 65 10 2 2 Removing the Module fr...

Page 5: ...t www wago com There you will find information regarding supply layout etc Pos 11 All e Seri en Allgemei ne Module Hi nweise zur D okumentati on Hinweise Hinweis Dokumentation aufbewahr en 4 mod_12379...

Page 6: ...l e Serien Allgemei ne Module Wichtige Erl uterungen Sicherheits und sonstige Hinweise Vorsicht Vorsicht _War nung vor Personensch den allgemein_ Erl uterung 13 mod_1343310028762_21 docx 101038 1 Pers...

Page 7: ...24V DC 0 5A IF 8xM8 Manual Version 1 1 0 Additional Information Refers to additional information which is not an integral part of this documentation e g the Internet Pos 13 5 Dokumentation allgemei n...

Page 8: ...ocx 21714 2 1 1 5 Font Conventions Table 2 Font Conventions Font Type Indicates italic Names of paths and data files are marked in italic type e g C Program Files WAGO Software Menu Menu items are mar...

Page 9: ...en Allgemei ne Dokumente Allgemei ne Module Wichtige Erl uterungen nderungsvor behalt berschrift 3 und Inhalt 3 mod_1221060036484_21 docx 21720 3 1 2 1 1 Subject to Changes WAGO Kontakttechnik GmbH Co...

Page 10: ...oriented module Note the Use of the Interference Free Module in Safety Applications chapter Pos 16 9 Serie 767 WAGO SPEED WAY Wichtige Erl uterungen I O M odul Bestimmungsgem e Verwendung 767 IOs all...

Page 11: ...Series component and the overall power consumption for all 767 components Neither of these values shall exceed 4 A since an increase in current causes the contacts to overheat and damages the 767 Seri...

Page 12: ...andards for EMC suitable installations For the power supply and for the S BUS use only pre assembled WAGO system cables so the specified characteristics of the technical data can be achieved Pos 16 20...

Page 13: ...ur system to protective earth PE and Pos 16 24 Serie 767 WAGO SPEED WAY Wichtige Erl uter ung en I O Modul Hinweise zum Betri eb 767 I O Teil 2 5 mod_1248180225875_21 docx 38755 1 Ensure that the cabl...

Page 14: ...o control solenoid valves gates transmitters relays or other electrical loads The module has many parameterization options that can be carried out via a fieldbus coupler In addition diagnostic message...

Page 15: ...ta from previous 767 Series components 2 S BUS output M12 socket B coded For transmitting S BUS data to the next 767 Series components or to the S BUS terminator Pos 18 7 Serie 767 WAGO SPEED WAY Ger...

Page 16: ...y Pos 18 11 Serie 767 WAGO SPEED WAY Ger tebeschr eibung Befestigung I O Module Legende zu Beschriftung und Befestigung 767 xxxx 5 mod_1249475777546_21 docx 40514 1 Table 4 Legend for figure Marking p...

Page 17: ...90 1 Table 5 Legend for figure Display elements Position LED Color Meaning 15 SB Green red orange S BUS status 16 F Red Diagnostic information Pos 18 16 Serie 767 WAGO SPEED WAY Ger tebeschr eibung An...

Page 18: ...g example Pos 18 19 3 Serie 767 WAGO SPEEDWAY Ger tebeschr eibung Bedr uckung I O M odul e Legende zur Bedr uckung 767 xxxx DO AO 5 mod_1248860045484_21 docx 39318 1 Table 6 Legend for figure Labeling...

Page 19: ...the module Pos 18 20 Serie 767 WAGO SPEED WAY Ger tebeschr eibung Bedr uckung I O M odul e Bedruckung sei tlich Legende 9 mod_1286969974465_21 docx 65601 1 Table 7 Description of manufacturing number...

Page 20: ...w of the power supply and principle of operation of the power supply connections as well as the digital outputs of the modules see also chapters Connecting the Supply Cable and Connecting the Actuator...

Page 21: ...Abmessungen berschrift 2 5 mod_1248869612468_21 docx 39441 2 1 3 6 Dimensions Pos 18 27 Serie 767 WAGO SPEED WAY Ger tebeschr eibung Abmessungen I O M odule Abmessungen 767 xxxx_IO_8xM 8 Bild 5 mod_12...

Page 22: ...g in this application Pos 18 31 Serie 767 WAGO SPEED WAY Ger tebeschr eibung Technische Daten I O M odule Digitalausgangsmodule Technische D aten 767 4801 5 mod_1248946002859_21 docx 39524 33333333333...

Page 23: ...of outputs 8 Connection type M8 connectors 3 poles Wire Connection 2 to 3 wire Output voltage UA Output current per channel 0 5 A max 0 6 A short circuit overload proof thermal disconnection Voltage d...

Page 24: ...Inductive load approx 20 Hz Resistive load approx 500 Hz Lamp load approx 500 Hz Recommended minimum load 50 mA Parallel connection of 2 outputs For power boost For redundant actuation of a load Type...

Page 25: ...data Diagnostics Per channel Actuator short circuit overload Per channel Interruption Wire break Actuator Per channel Over temperature Per module Undervoltage ULS UA 3 7 9 Process Image Table 16 Tech...

Page 26: ...gen cU Lus UL508 3 mod_1224055013140_0 docx 24020 1 CULUS UL508 Pos 18 33 3 3 D okumentati on allgemein Gli ederungsel emente Leerzeil e 3 mod_1224662755687_0 docx 24460 1 Pos 18 33 4 Serie 767 WAGO S...

Page 27: ...1 Ex Directive 94 9 EC Pos 18 35 7 Alle Serien Allgemeine M odul e Nor men und Richtlini en Ex i Nor men Explosionsf hig e Atmosph r e EN 60079 0 14 mod_1360841627885_21 docx 111880 1 Explosive atmosp...

Page 28: ...eise 767 xxxx allgemei n_1 5 mod_1249028727125_21 docx 39643 2 1 4 1 Information on Mounting The following information shall always be observed Disconnect the power supply from the system before you s...

Page 29: ...523_21 docx 196008 1 Any mounting position is possible Ensure a safe mounting position In explosion hazardous environments no increased mechanical loads must be present at the installation location If...

Page 30: ...bus manuals in the Accessories section Select the manual appropriate to the fieldbus you are using Carrier rail adapter including fixing screws and perforated or imperforated carrier rails DIN rail 35...

Page 31: ...nect all cable without problems Pos 21 11 Serie 767 WAGO SPEED WAY Wichtige Erl uter ung en Sicherheitshinweise Hinweis Hi nweis 767 xxxx Distanzst ck 8 mod_1279025151416_21 docx 59810 1 Direct Mounti...

Page 32: ...rier Rail Adapter to the Module A carrier rail adapter is required to mount the module on carrier rails Screw together the module and carrier rail adapter using the M4 threaded screws provided as show...

Page 33: ...onnect the power supply from those devices on which you wish to mount the module 2 Set the module onto the edge of the carrier rail 51 with the two notches 50 3 Press the undersurface against the lowe...

Page 34: ...you also have the option to fasten it to a profile rail using the profile adapter and nuts provided that this mounting type is supported by your system You are to supply the necessary nuts Screw toge...

Page 35: ...m two nuts are required with one screw each length of screw threads must be compatible with your system 1 Disconnect the power supply from those devices on which you wish to mount the module 2 Insert...

Page 36: ...slot width 3mm into the small opening under the marking strip cover 12 and lever it up 2 Remove the marking strip cover 3 Mark the marking strip with a waterproof pen 4 Reinsert the marking strip cove...

Page 37: ...included on the spacer for cable ties 1 Disconnect the power supply from those devices on which you wish to mount the module 2 The spacer can only be inserted into the appropriate openings of the modu...

Page 38: ...one 767 component connected with a spacer can be attached and screwed on to the preceding component due to the mounting direction The last 767 component is fastened without a spacer Pos 21 33 Serie 7...

Page 39: ...onent can be found in the corresponding data sheet which is available from www wago com Pos 23 5 Serie 767 WAGO SPEED WAY Wichtige Erl uterungen Sicherheitshinweise Achtung Achtung Offene Anschl sse 8...

Page 40: ...ng radiuses of the WAGO system cable For more information see the technical data at www wago com When laying all cable ensure that you do not lay it in shear areas of moving machine parts Observe the...

Page 41: ...d for communication between a fieldbus coupler and the connected 767 Series components Requirement A WAGO S BUS cable pre assembled on both ends is readily available to you This is necessary for optim...

Page 42: ...ules have been connected to the fieldbus coupler connect the S BUS cables S1 S2 to the associated IN and OUT connections as shown in the following figure 3 Tighten the plugs and sockets using the knur...

Page 43: ...24 VDC UA 3 0 V ULS 4 0 V UA Pos 23 16 Serie 767 WAGO SPEED WAY Wichtige Erl uter ung en Sicherheitshinweise Achtung Achtung H chste Strombel astbar keit der Versorgungskontakte 8 mod_1278308653219_21...

Page 44: ...been connected to the fieldbus coupler connect the power supply transmission cable K1 K2 with the associated IN and OUT connections as shown in the following figure 3 Tighten the plugs and sockets us...

Page 45: ...g table outlines the assignment of the actuator connections Table 21 Connection assignment of digital outputs Connection Connection diagramm OUT OUT X1 X3 X5 X7 X2 X4 X6 X8 Pos 23 22 Serie 767 WAGO SP...

Page 46: ...r supply from those devices on which you have mounted the module 2 Insert the actuator cable plug into an output socket 3 of the module and tighten it via knurled head screw 3 Screw a protective cap o...

Page 47: ...which must be ordered separately in order to maintain the IP67 degree of protection See section Accessories of the fieldbus coupler controller manual Pos 27 Serie 767 WAGO SPEED WAY In Betrieb nehmen...

Page 48: ...n a dangerous state and personnel and machines could be at risk Before changing the parameters ensure that the machine components are in a safe and defined state and switch off the higher level contro...

Page 49: ...nly Writes the modified values to the module Close Online and offline mode Closes the parameterization user interface DTM Apply Offline mode only Applies the entries in the project Please note that th...

Page 50: ...ufacturer Release index FW HW FL FW Actual firmware release index When updating the firmware please note that the firmware release index may not be conformed to the printed firmware release index on t...

Page 51: ...fer from the actual module Pos 30 7 Serie 767 WAGO SPEED WAY Par ametrieren I O M odule Parametri erung 767 xxxx Di agnose bersicht_2 7 mod_1265811272140_21 docx 50279 1 Table 24 Diagnostics setup Par...

Page 52: ...0 Serie 767 WAGO SPEED WAY Parametrier en I O Module Parametrier ung Kanaldi agnosen Kurzschl uss berlast Aktor 8 mod_1278414485725_21 docx 59134 1 Table 26 Information about an existing channel diagn...

Page 53: ...40292 1 Table 27 Overview of adjustable parameters for the digital outputs Parameter Description Designation Electronic marking field max 40 characters Output value This value is released to the outp...

Page 54: ...1 The output is only switched on again after you confirm the diagnostic message Restart delay actuator Time in 100 ms intervals after which a disabled output is switched on again in case of error You...

Page 55: ...cription Simulation diagnostic If the checkbox is selected you can simulate a low voltage diagnostic To generate a low voltage diagnostic one or both of the two checkboxes Low voltage ULS and Low volt...

Page 56: ...be replaced due to a defect you do not need to reconfigure the new I O module The stored parameters are automatically transferred to the new I O module Detailed information on this procedure can be f...

Page 57: ...coupler that supports the synchronous diagnostic function e g 767 1101 or 767 2301 Detailed information about enabling the transmission of diagnostic information can be found in the manual for the fie...

Page 58: ...hort circuit overload on channel 1 confirmed 1B Actuator short circuit overload on channel 2 confirmed 1B Actuator short circuit overload on channel 3 confirmed 1B Actuator short circuit overload on c...

Page 59: ...channel 3 confirmed 1B Overtemperature on channel 4 confirmed 1B Overtemperature on channel 5 confirmed 1B Overtemperature on channel 6 confirmed 1B Overtemperature on channel 7confirmed 1B Overtempe...

Page 60: ...ad on channel 3 1B Actuator short circuit overload on channel 4 1B Actuator short circuit overload on channel 5 1B Actuator short circuit overload on channel 6 1B Actuator short circuit overload on ch...

Page 61: ...Byte 3 7 0 Diagnostic message 1B Undervoltage ULS 1B Undervoltage UA Diagnostic messages Normally both Actuator short circuit and Overtemperature diagnostic messages are issued simultaneously Pos 39...

Page 62: ...nostics Use the diagnostic overview section Parameterizing Diagnostic Overview to disable specific diagnostics see F and I O LED In this case the corresponding LED is disabled off Pos 42 3 Serie 767 W...

Page 63: ...Hz The S BUS parameters are being stored by the fieldbus coupler Orange The firmware is being updated All 767 Series components are being updated by the fieldbus coupler within the node Orange flashin...

Page 64: ...be diagnosed an interruption cannot If the output is switched off only an interruption detection can be diagnosed line break If you set the time of the parameter Restart delay actuator section Parame...

Page 65: ...eplacing the Module To replace a module e g to change variants proceed as described follow 10 2 1 Disconnecting the Cables Before removing the connectors clean the module to ensure that no dirt or oth...

Page 66: ...2 3 Removing the Module from the Carrier Rail In order to keep the representation unambiguous the carrier rail adapter in the following figure B C is shown without module If the module is mounted on...

Page 67: ...nd remove the module from the profile rail of your system 3 Unscrew the screws that connect the module with the profile adapter 10 2 5 Connecting the Module To connect the module proceed as described...

Page 68: ...atz in sicherheitsg erichteten Anwendung en 767 xxxx_Wichtige Hinweise_2 11 mod_1317280411044_21 docx 80000 2 1 11 1 Important Notes Only use SELV PELV power supplies Only a power supply unit with pro...

Page 69: ...must be tightened at a torque of 0 6 Nm Otherwise the safe shutdown of the I O module by a safety switching device in the case of penetrating pollution cannot be ensured Observe connecting cable speci...

Page 70: ...error UA and ULS can each be protected using a safety fuse according to EN 60127 2 or electronic fuse e g WAGO 787 861 Safety fuses according to EN 60127 2 must meet the following technical requireme...

Page 71: ...EN 60204 1 or EN ISO 13849 2 The shield must have an overlap of at least 85 and be reliably connected to the connector Attach ground shield or use insulation monitoring The connecting lead ground shi...

Page 72: ...u use unshielded connecting cables to supply interference free modules you are required to install the connecting cables according to EN 60204 1 or EN ISO 13849 2 in a cable duct armored conduit or sh...

Page 73: ...the interference free module in safety related applications you must combine the interference free modules belonging to one safety switching device in a potential group The power supply UA of the int...

Page 74: ...gure 26 Single pin shutdown of the power supply of all digital outputs Figure 27 Two pin shutdown of the power supply of all digital outputs Pos 60 D okumentation allgemei n Glieder ungselemente Seite...

Page 75: ...agnostic codes can be generated by the module Table 33 Diagnostics of the module Diagnostic Message Attribute Path Classification C I A Low voltage ULS sensor supply 50 1 128 Diagnostic alarm Low volt...

Page 76: ...Attaching another module with a spacer 38 Figure 15 S BUS connected to a fieldbus coupler and modules 42 Figure 16 Supply cable connected to a fieldbus coupler and modules 44 Figure 17 Connectors exem...

Page 77: ...es on Output 24 Table 14 Technical data Configurable Functions 25 Table 15 Technical data Diagnostics 25 Table 16 Technical data Process Image 25 Table 17 Technical data Display Elements 25 Table 18 T...

Page 78: ...te 2015 9 mod_1285229376516_21 docx 64944 1 WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 05 71 8 87 0 Fax 05 71 8 87 1 69 E Mail info wago com Intern...

Reviews: