82
Parameterizing
WAGO-TO-PASS® 761
761-217 Telecontrol Module Compact, 8 AI, Web, MODBUS485
Manual
Version 1.0.0
7.9.1
MODBUS Settings
Select the
TO-PASS
®
telecontrol module from the project tree using the identifier.
Select the
MODBUS Settings
option under the
MODBUS
entry.
The buttons for the MODBUS format and the input field for the polling cycle time
are provided on the right side:
Figure 36: Configuring the MODBUS settings
Table 38: Configuring the MODBUS settings
Enable/Format
MODBUS format Select the transmission format for MODBUS
communication; the format selected must be compatible with
the controller used.
The following formats are possible:
Not used (no MODBUS connection)
9600 (8N2), RTU Input (0x04)
9600 (8E1), RTU Input (0x04)
9600 (8O1), RTU Input (0x04)
9600 (8N1), RTU Input (0x04)*
9600 (8N2), RTU Holding (0x03)*
9600 (8E1), RTU Holding (0x03)*
9600 (8O1), RTU Holding (0x03)*
9600 (8N1), RTU Holding (0x03)*
19200 (8N2), RTU Input (0x04)*
19200 (8E1), RTU Input (0x04)*
19200 (8O1), RTU Input (0x04)*
19200 (8N1), RTU Input (0x04)*
19200 (8N2), RTU Holding (0x03)*
19200 (8E1), RTU Holding (0x03)*
19200 (8O1), RTU Holding (0x03)*
19200 (8N1), RTU Holding (0x03)*
* These functions are available starting with Firmware
Version FW 2.33.
Polling cycle
Here, enter the MODBUS subscriber polling cycle time in
multiples of 10 ms.
The requested MODBUS subscriber must reply within this
time. This means that the polling cycle time is a function of
the response time of the slowest subscriber.