Random Address

 

The "Random address" (or "Search Address") is a 24-bit address generated 
by an ECG during initialization. 

Replace Function

 

In the event that exactly one control gear item (ECG) is defective and is 
replaced by a non-addressed ECG, the "Replace" function can be used to 
automatically assign the old short address of the previous control gear to the 
new control gear and subsequently restore the settings for that control gear 
using the data stored in the module database.

 

 

 

Single Master

 

In contrast to a Multi-Master, a "Single Master" does not support collision 
detection and is not suitable for connection at the same interface with other 
masters. 

Settling Time

 

The "Settling Time" is the minimum time period between two frames. 

 V 

 

 

Virtual Group

 

A DALI group is a logical combination of devices to which a common 
group address is assigned so that these devices execute a common function 
synchronously. These devices do not necessarily have to be physically 
linked (e.g., the group for all emergency lighting systems, all hallway lights, 
etc.).  
In the event that the 16 group addresses available for this (0 ... 15) are not 
sufficient, as further groups are required, an additional 16 virtual groups 
(with group addresses 17 .... 31) can also be created. These groups cannot, 
however, be addressed via a DALI group command, but only one after the 
other by individual commands from the DALI-Multi-Master module. A 
maximum of 8 devices may be assigned to each virtual group in order not 
slow down or impede DALI data exchange on the bus. 

Pos: 82 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @  @ 1 

 

Summary of Contents for 753-647

Page 1: ...66_0 doc 64941 1 Manual WAGO I O SYSTEM 750 DALI Multi Master Module 753 647 Version 1 0 0 Pos 3 Alle Serien Allgemeine Module Hinweise zur Dokumentation Impressum f r Standardhandb cher allg Angaben...

Page 2: ...0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we always...

Page 3: ...re 13 2 3 2 PC Software 13 2 3 3 WAGO I O SYSTEM 14 3 Device Description 15 3 1 Device Specific Safety Information 15 3 2 Abbreviations and Terms 16 3 3 General Description 17 3 4 View 20 3 5 Connecto...

Page 4: ...ccessing the DALI Multi Master Module 50 7 3 Module Configuration Notes 50 7 4 Data Management Notes 51 7 5 Configuring the DALI Network Using the WAGO DALI Configurator Basic Procedure 51 8 Diagnosti...

Page 5: ...TEM Hinweise zur Dokumentation Hinweise Achtung Hinweis zur Dokumentation Busklemmen 750 xxxx 4 mod_1237986979656_21 doc 29023 1 The I O module 753 647 shall only be installed and operated according t...

Page 6: ...sult in death or serious injury Personal Injury Indicates a moderate risk potentially hazardous situation which if not avoided could result in death or serious injury Personal Injury Indicates a low r...

Page 7: ...Multi Master Module Manual Version 1 0 0 Additional Information Refers to additional information which is not an integral part of this documentation e g the Internet Pos 11 4 Dokumentation allgemein G...

Page 8: ...e 2 Font Conventions Font type Indicates italic Names of paths and data files are marked in italic type e g C Programme WAGO I O CHECK Menu Menu items are marked in bold letters e g Save A greater tha...

Page 9: ...SYSTEM Wichtige Erl uterungen Personalqualifikation 750 xxxx 3 mod_1224061208046_21 doc 24063 3 1 2 1 2 Personnel Qualifications All sequences implemented on Series 750 devices may only be carried ou...

Page 10: ...te berschrift 3 und Inhalt 3 mod_1221060446109_21 doc 21723 3 1 2 1 4 Technical Condition of Specified Devices The components to be supplied Ex Works are equipped with hardware and software configurat...

Page 11: ...verh tungsvorschriften beachten 6 mod_1260180657000_21 doc 46735 1 Pos 14 10 4 Alle Serien Allgemeine Module Wichtige Erl uterungen Sicherheits und sonstige Hinweise Gefahr Gefahr Auf normgerechten An...

Page 12: ...ction lines Avoid reverse polarity of data and power supply lines as this may damage the devices involved Pos 14 11 6 Alle Serien Allgemeine Module Wichtige Erl uterungen Sicherheits und sonstige Hinw...

Page 13: ...berschriften f r alle Serien Wichtige Erl uterungen PC Software berschrift 3 12 mod_1339753791838_21 doc 97776 3 1 2 3 2 PC Software Pos 17 4 Serie 759 WAGO Software WAGO DALI Configurator Tabelle Erf...

Page 14: ...753 0647 12 mod_1340040395421_21 doc 98016 1 Table 6 Required Hardware of the WAGO I O SYSTEM Component Reference Source Order number Fieldbus controller PLC WAGO I O SYSTEM 750 e g ETHERNET PLC 750...

Page 15: ...cal isolation for this between the DALI bus and the I O module required for the installation of 230V electrical loads DALI slaves can be destroyed on misuse of the 787 1007 power supply unit The WAGO...

Page 16: ...Table 7 Abbreviations and terms used in this manual Abbreviation Term Explanation Control Device IEC term for the DALI Multi Master also active sensors Control Gear IEC term for passive electronic bal...

Page 17: ...mplex lighting scenes to be implemented with group functions Using the WAGO I O SYSTEM DALI control devices are seamlessly integrated with all supported BA and fieldbus protocols Figure 1 Overview of...

Page 18: ...for this After successful address allocation 16 groups and 16 scenes can be assigned to each of the DAL ECGs A further 16 virtual groups can also be configured on the DALI bus The WAGO I O PRO progra...

Page 19: ...Easy Mode The Easy mode is the standard state for the DALI Multi Master module The Full mode can be activated via PLC modules or using the WAGO I O CHECK software Eight colored LEDs on the I O module...

Page 20: ...Meaning For details see Section 1 Marking options using the Mini WSB 2 A H Status LEDs Device Description Display Elements 3 Data contacts Device Description Connections 4 1 5 CAGE CLAMP Connections D...

Page 21: ...f cleaning gold spring contacts Figure 3 Data contacts Pos 27 2 Serie 750 WAGO I O SYSTEM Wichtige Erl uterungen Sicherheitshinweise Achtung Achtung Busklemmen nicht auf Goldfederkontakte legen 7 mod_...

Page 22: ...of downstream I O modules Pos 32 Serie 750 WAGO I O SYSTEM Ger tebeschreibung Anschl sse CAGE CLAMP Anschl sse berschrift 3 6 mod_1256296337770_21 doc 43674 3 1 3 5 3 CAGE CLAMP Connections Pos 33 Se...

Page 23: ...ase was not read I O module has no current configuration function may therefore be limited A Easy Mode Yellow Addressed device found no current configuration read Green flashing Signal transmission Tx...

Page 24: ...g relay function On H Firmware update Yellow flashing Firmware update being performed Pos 37 Alle Serien Allgemeine Module berschriften f r alle Serien Ger tebeschreibung Bedienelemente berschrift 2 4...

Page 25: ...240984441312_21 doc 31967 2 1 3 8 Schematic Diagram Pos 41 Serie 753 WAGO I O SYSTEM Ger tebeschreibung Schematisches Schaltbild Schematisches Schaltbild 753 0647 11 mod_1328523032881_21 doc 87744 1 7...

Page 26: ...y Table 12 Technical Data Supply Power supply via system voltage 5 V DC Current consumption internal 30 mA Module power supply at U and U 18 V via 753 620 or 787 1007 Power Supplies Guaranteed supply...

Page 27: ...2770233112_21 doc 92133 1 acc to EN 61241 0 2006 and acc to EN 61241 1 2004 os 54 Dokumentation allgemein Gliederungselemente Leerzeile 3 mod_1224662755687_0 doc 24460 1 Pos 55 Alle Serien Allgemeine...

Page 28: ...guration in WAGO I O PRO The Easy mode is the set default This mode must also be used if no program is being used that has a DALI master module The mode setting is not permanently stored in the DALI M...

Page 29: ...a permanently updated internal database of the module when configured The operating hours of the devices active times of the lights are also recorded When a defective electronic ballast ECG must be r...

Page 30: ...s switched off Table 14 Control of lighting via buttons Buttons Press Description short Switch lighting ON ON rocker switch long Dim lighting brighter short Switch lighting OFF OFF rocker switch long...

Page 31: ...g Brighter Darker dimming Status ON OFF ON OFF Status No error Error DA1 short ON OFF long Brighter Darker dimming Status ON OFF ON OFF Status No error Error DA2 short ON OFF long Brighter Darker dimm...

Page 32: ...F long Brighter Darker dimming Status ON OFF ON OFF Status No error Error DA15 short ON OFF long Brighter Darker dimming Status ON OFF Byte 5 ON OFF Status No error Error DA16 short ON OFF long Bright...

Page 33: ...F long Brighter Darker dimming Status ON OFF ON OFF Status No error Error DA31 short ON OFF long Brighter Darker dimming Status ON OFF Byte 9 ON OFF Status No error Error DA32 short ON OFF long Bright...

Page 34: ...FF long Brighter Darker dimming Status ON OFF ON OFF Status No error Error DA47 short ON OFF long Brighter Darker dimming Status ON OFF Byte 13 ON OFF Status No error Error DA48 short ON OFF long Brig...

Page 35: ...ON OFF long Brighter Darker dimming Status ON OFF ON OFF Status No error Error DA63 short ON OFF long Brighter Darker dimming Status ON OFF Byte 17 ON OFF Status No error Error GA0 short ON OFF long B...

Page 36: ...t ON OFF long Brighter Darker dimming Status ON OFF ON OFF Status No error Error GA13 short ON OFF long Brighter Darker dimming Status ON OFF ON OFF Status No error Error GA14 short ON OFF long Bright...

Page 37: ...arefully to prevent injury Pos 65 3 Serie 750 WAGO I O SYSTEM Wichtige Erl uterungen Sicherheitshinweise Achtung Achtung Busklemmen in vorgegebener Reihenfolge stecken 6 mod_1256194177073_21 doc 43429...

Page 38: ...und Conductor in manual System Description WAGO I O SYSTEM 750 Pos 65 9 Alle Serien Allgemeine Module Wichtige Erl uterungen Sicherheits und sonstige Hinweise Achtung Achtung Arbeiten an Ger ten nur s...

Page 39: ...ious or possibly subsequent I O module are established Pos 65 11 Serie 750 WAGO I O SYSTEM Montieren Busklemme entfernen 4 mod_1239169375203_21 doc 30334 3 1 5 2 2 Removing the I O Module 1 Remove the...

Page 40: ...gged into the bottom of the module The connector can be completely removed together with the wiring simplifying replacement of defective modules from the assembly Figure 9 Connector and module Miniatu...

Page 41: ...stic pins and sockets facilitates mating of the module with the appropriate connector 1 Insert the pin into the socket Figure 12 Assembling the coding pins 2 Position the assembled coding pins in the...

Page 42: ...hen the connector is removed the sockets remain in the I O module The coded connector can only fit in the corresponding coded I O module see figures below Figure 15 Sure match coding pins Pos 65 16 Do...

Page 43: ...module by pulling the orange pull tab on the connector toward the top of the module Figure 16 Pulling the pull tab The connector detaches from the module Figure 17 Removing the connector without tool...

Page 44: ...conductor at one single connection If more than one conductor must be routed to one connection these must be connected in an up circuit wiring assembly for example using WAGO feed through terminals E...

Page 45: ...les in the node will not be passed to the following modules A supply module is therefore required to provide any additional I O modules 6 2 2 Module Supply Required accessories DC DC converter Item No...

Page 46: ...third 753 620 DC DC converter to provide proper power supply to further DALI Multi Master modules at the fieldbus node In this configuration ensure that the DC DC converters are initially installed ad...

Page 47: ...modules Abbildung 22 Anschaltprinzip Stromversorgung 787 1007 mit f nf DALI Multi Master Klemmen 6 2 3 DALI Bus Line The DALI bus control line consists of one pair of conductors which can be run toge...

Page 48: ...installed is yielded from calculating the total power consumption and from the number of addresses for each sensor The topology of the DALI bus is not defined Line tree star or mixed structures are po...

Page 49: ...e consists of the following WAGO I O SYSTEM components Table 19 Example of a fieldbus node setup Item number Designation 750 881 Programmable Fieldbus Controller ETHERNET PLC 753 620 DC DC converter 7...

Page 50: ...communication link must be set up via the IP address of the WAGO PLC connected at the fieldbus node to ensure proper data exchange with the DALI Multi Master module via the WAGO DALI Configurator You...

Page 51: ...essing buttons in the WAGO DALI Configurator toolbar 2 Add DALI devices to the tree structure Before beginning configuration you must add devices from the device list to the tree structure left dialog...

Page 52: ...A detailed description of the software and the individual configuration steps using the WAGO DALI Configurator is given in the corresponding manual You can download the WAGO DALI Configurator manual f...

Page 53: ...on Display Elements You can also perform diagnostics for all DALI network subscribers located in the connected DALI line using the WAGO DALI Configurator configuration software A list of devices is ge...

Page 54: ...uplicate addresses select the devices with the identical addresses and then point to the function Delete selected duplicate addresses in the selection list on the right below the table Then click the...

Page 55: ...erie 750 3 mod_1234272230203_21 doc 27500 1 The WAGO I O SYSTEM 750 electrical equipment is designed for use in Zone 2 hazardous areas The following sections include both the general identification of...

Page 56: ...ugelassenen Busklemmen gem CENELEC und IEC 7 mod_1274340031573_21 doc 56687 1 Figure 25 Side marking example for ATEX and IEC Ex approved I O modules according to CENELEC and IEC Figure 26 Printing Te...

Page 57: ...in Ex Bereichen Beispielbedruckung der Ex i und IEC Ex i zugelassenen Busklemmen gem CENELEC und IEC 7 mod_1274338578856_21 doc 56679 1 Figure 27 Side marking example for Ex i and IEC Ex i approved I...

Page 58: ...rding to Procedure A use in Zone 22 IP6X Dust tight totally protected against dust T 135 C Max surface temp of the enclosure no dust bin Mining I Device group Mining M2 Device category High degree of...

Page 59: ...elbedruckung gem NEC 500 7 mod_1274339607920_21 doc 56683 1 Figure 29 Side marking example for I O modules according to NEC 500 Figure 30 Text detail Marking example for I O modules according to NEC 5...

Page 60: ...ts with rated voltages above 1 kV DIN VDE 0800 Installation and operation in telecommunication plants including information processing equipment DIN VDE 0185 lightning protection systems The USA and C...

Page 61: ...ations I O module 750 440 may be used up to max 120 V AC When used in the presence of combustible dust all devices and the enclosure shall be fully tested and assessed in compliance with the requireme...

Page 62: ...rating voltage is not being exceeded of more than 40 because of transient disturbances 3 DIP switches binary switches and potentiometers connected to the module may only be actuated when explosive at...

Page 63: ...Do not remove or replace fuse when energized If the module is energized do not remove or replace the fuse Pos 78 26 Alle Serien Allgemeine Module Wichtige Erl uterungen Sicherheits und sonstige Hinwe...

Page 64: ...cause of transient disturbances 3 DIP switches binary switches and potentiometers connected to the module may only be actuated when explosive atmosphere can be excluded 4 The connecting and disconnect...

Page 65: ...Do not remove or replace fuse when energized If the module is energized do not remove or replace the fuse Pos 78 33 Alle Serien Allgemeine Module Wichtige Erl uterungen Sicherheits und sonstige Hinwe...

Page 66: ...ardous near each operator accessible connector and fuse holder When a fuse is provided the following information shall be provided A switch suitable for the location where the equipment is installed s...

Page 67: ...s 78 38 Dokumentation allgemein Gliederungselemente Leerzeile 3 mod_1224662755687_0 doc 24460 1 Pos 78 39 Dokumentation allgemein Gliederungselemente Leerzeile 3 mod_1224662755687_0 doc 24460 1 Pos 78...

Page 68: ...C designation for the DALI Multi Master This term also denotes the active sensors D DALI DALI is the acronym for Digital Addressable Lighting Interface a protocol for control of lighting devices and e...

Page 69: ...2 Discharge Lamps 204 Device Type 3 Low Voltage Halogen Lamps 205 Device Type 4 Incandescent Lamps 206 Device Type 5 Conversion of Digital Signals to DC Voltage 207 Device Type 6 LED Modules 208 Devic...

Page 70: ...Time The Settling Time is the minimum time period between two frames V Virtual Group A DALI group is a logical combination of devices to which a common group address is assigned so that these devices...

Page 71: ...ghting Interface Part 100 General Requirements 62386 101 System PUB 1 Ed published 06 09 62386 102 Control Gear PUB 1 Ed published 06 09 936 DC for Amdt 1 commenting date 29 10 2010 Digital Addressabl...

Page 72: ...er 43 Figure 1 Connecting a conductor to a CAGE CLAMP 44 Figure 3 Configuration diagram for the 753 620 DC DC converter with one DALI Multi Master module 46 Figure 4 Configuration diagram for three 75...

Page 73: ...output process image in the Easy mode 30 Table 5 Overview of input process image in the Easy mode 30 Table 6 Output and input process image for the DALI Multi Master module in the Easy mode 31 Table 1...

Page 74: ...te 9 mod_1285229376516_21 doc 64944 1 WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 49 5 71 8 87 0 Fax 49 5 71 8 87 1 69 E Mail info wago com Internet...

Reviews: