58
Use in Hazardous Environments
WAGO-I/O-SYSTEM 750
753-647 DALI Multi-Master Module
Manual
Version 1.0.0
Table 22: Description of marking example for Ex i and IEC Ex i approved I/O modules according to
CENELEC and IEC
Inscription text
Description
TÜV 07 ATEX 554086 X
TUN 09.0001X
Approving authority or
certificate numbers
Dust
II
Device group: All except mining
3(1)D
Device category: Zone 22 device (Zone 20 subunit)
Ex
Explosion protection mark
tD
Protection by enclosure
[iaD]
Approved in accordance with "Dust intrinsic safety"
standard
A22
Surface temperature determined according to
Procedure A, use in Zone 22
IP6X
Dust-tight (totally protected against dust)
T 135°C
Max. surface temp. of the enclosure (no dust bin)
Mining
I
Device group: Mining
(M2)
Device category: High degree of safety
[Ex ia]
Explosion protection: Mark with category of type of
protection intrinsic safety: Even safe when two
errors occur
I
Device group: Mining
Gases
II
Device group: All except mining
3(1)G
Device category: Zone 2 device (Zone 0 subunit)
Ex
Explosion protection mark
nA
Type of protection: Non-sparking operating
equipment
[ia]
Category of type of protection intrinsic safety: Even
safe when two errors occur
IIC Explosion
Group
T4
Temperature class: Max. surface temperature 135°C
Pos: 78.9 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1