Technical Data
• 9
Fieldbus Dependent I/O Module
PROFIBUS DP
Climatic Environmental Conditions
Operating temperature
0 °C ... 55 °C
Storage temperature
-25 °C ... +70 °C
Relative air humidity
10 ... 45 % , no dew formation
Air pressure in operation
86 ... 106 hPa
Maximum altitude
max. 2000 m above sea level
Strain by harmful substances
Inspection according to IEC 60068-2-42 and
IEC 60068-2-43
Special conditions
Exercise caution when subjecting the I/O modules to
the following conditions:
– dust, corrosive vapors or gasses
– ionized radiation.
Mechanical Strength
Vibration
According to IEC 60068-2-6, inspection Fc
10 ... 57 Hz constant amplitude 0.075 mm
57 ... 150 Hz constant acceleration 1 g
Impact
According to IEC 60068- 2-27; 15 g, 11 ms
Electrical Safety
Reverse voltage protection
Yes
Air and creepage distances
According to DIN EN 61131-2 and DIN EN 50178
between current circuits and body as well as between
electrically isolated, separate current circuits, accord-
ing to over-voltage category II, degree of pollution 2
Isolation
Yes, between fieldbus and internal electronics
Test voltage
DC 500 V
Electromagnetic Compatibility
Interference Resistance according to EN50082-2 : 1995
EN 61000-4-2
4kV/8kV
(2/4)
B
EN 61000-4-3
10V/m 80% AM
(3)
A
EN 61000-4-4
2kV
(3/4)
B
EN 61000-4-6
10V/m 80% AM
(3)
A
Interference emission according to EN50081-2 : 1994
EN 55011
30 dBµV/m
(30 m)
37 dBµV/m