WAGO I/O System Compact
Properties 29
751-9301 Compact Controller 100
Manual
Version 1.1.0, valid from FW Version 03.08.07(20)
Table 8: Digital outputs – “X5”
Contact
Signal
Description
1
U
in
+
Supply voltage input (DO1 … DO4)
2
0V
Ground
3
DO1
Digital output 1
4
0V
Ground
5
DO2
Digital output 2
6
0V
Ground
7
DO3
Digital output 3
8
0V
Ground
9
DO4
Digital output 4
10
0V
Ground
4.1.3.5 Analog inputs and outputs
The connectors are for connecting actuators and sensors.
picoMAX
®
plugs with push-in CAGE CLAMP
®
S connections are used.
4.1.3.5.1 Analog inputs
The controller processes signals with standardized values of 0 … +10 V from the
field range.
The product has 2 input channels for field signals.
The sensors are connected to AI1 and ground or AI2 and ground in each case.
The ground connections are available for both channels on a common 0V ground
potential.
The input signal is transmitted at a resolution of 16 bits.
The internal power supply powers the module.
Table 9: Analog inputs – “X14”
Contact
Signal
Description
1
AI1
Analog input 1
2
GND
Ground
3
AI2
Analog input 2
4
GND
Ground