34 Ground Fault Diagnostics
WAGO-I/O-SYSTEM 750
750-626/020-002 Power Supply Filter 24 VDC HI GF
Manual
Version 1.0.0
Table 14: Internal Resistance (DC) of the Test Circuit and Threshold with Ground Fault
State
Operating
Module
(System, Ship)
Internal
Resistance (DC)
Test Circuit
Thresholds with
Ground Fault
Ground diagnostics
disabled
Normal operation >10 MΩ
-
Ground fault
enabled
Commissioning,
maintenance
>90 kΩ
Pre-alarm
50 kΩ (typ.)
Main alarm
25 kΩ (typ.)
If enabled, possible ground faults are continuously monitored and reported via
the input process image. The diagnostic messages may change during the test
period. “VAL”=1 in the input process image signals a valid ground fault test.
6.1
Process Image
Table 15: Input Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0V_MA
0V_PA
24V_MA 24V_PA not used PWR_DIAG not used VAL
Table 16: Explanation of “Input Process Image”
Bit Value
Explanation
VAL
“0” Ground fault diagnostics disabled or field voltage not available or
transient phase not completed
“1” Ground fault diagnostics enabled and field voltage available and
transient phase completed
not used
Not used
PWR_DIAG
“0” Field voltage available
“1” Field voltage not available
not used
Not used
24V_PA
Pre-alarm 24 V
24V_MA
Main alarm 24 V
0V_PA
Pre-alarm 0 V
0V_MA
Main alarm 0 V