WAGO-I/O-SYSTEM 750
Ground Fault Diagnostics 37
750-626/020-002 Power Supply Filter 24 VDC HI GF
Manual
Version 1.0.0
Figure 15: WAGO-I/O-
CHECK
– Ground Fault Diagnostics Dialog, Diagnostics Enabled
Ground fault diagnostics is enabled.
Note
Changes possible during ground fault diagnostics!
Enabled ground fault diagnostics is indicated as follows:
• In WAGO-I/O-
CHECK
:
By the “Diagnostics enabled” message in the dialog.
• In the input process image:
Bit "VAL=1" (The measuring circuit is switched on and the transient
phase is completed.)
The diagnostic messages may change during the test period. Ground fault
diagnostics are not saved on the device.
If a ground fault is detected against the +24V field or 0V field potential, the
fault is indicated in the dialog.
Figure 16: WAGO-I/O-
CHECK
– Ground Fault Diagnostics Dialog, Pre-Alarm 24V