![WAGO 750-458 Manual Download Page 44](http://html1.mh-extra.com/html/wago/750-458/750-458_manual_868439044.webp)
44 Process Image
750-458 8AI; TC; Adjust
Manual
Version 1.3.0
For the voltage measurement with sensor type ±120 mV (ID11), the input range
of −120
mV … +120
mV is mapped to a value range of −24000
… +24000 at a
resolution of 0.005 mV. Voltage values below 0 mV are represented in two's
complement binary. The voltage underranges and overranges refer to
manufacturer range violations.
Table 31: Process Image Voltage Measurement ±120 mV, ID11, Two's Complement
Representation
Voltage
mV
Numeric value
1)
Status
Byte
Hex.
Error
LED
Binary
Hex.
Dec.
< −120.0
'1010.0010.0100.0000'
0xA240
−24000
0x41
ON
Underrange
−120.0
'1010.0010.0100.0000'
0xA240
−24000
0x00
OFF
−90.0
'1011.1001.1011.0000'
0xB9B0
−18000
0x00
OFF
−60.0
'1101.0001.0010.0000'
0xD120
−12000
0x00
OFF
−30.0
'1110.1000.1001.0000'
0xE890
−6000
0x00
OFF
0.0
'0000.0000.0000.0000'
0x0000
0
0x00
OFF
30.0
'0001.0111.0111.0000'
0x1770
6000
0x00
OFF
60.0
'0010.1110.1110.0000'
0x2EE0
12000
0x00
OFF
90.0
'0100.0110.0101.0000'
0x4650
18000
0x00
OFF
120.0
'0101.1101.1100.0000'
0x5DC0
24000
0x00
OFF
Overrange
'0101.1101.1100.0000'
0x5DC0
24000
0x42
ON
> 120.0
Wire break
'0111.1111.1111.1111'
0x7FFF
32767
0x60
ON
---
1)
Temperature values below 0 °C are represented in two's complement binary.