![WAGO 750-458 Manual Download Page 33](http://html1.mh-extra.com/html/wago/750-458/750-458_manual_868439033.webp)
Process Image 33
750-458 8AI; TC; Adjust
Manual
Version 1.3.0
4.2
Status Bytes
Status bytes are identically implemented for all channels. Therefore, the following
description in this section applies to all status bytes of the I/O module.
Table 19: Status Byte CH1_S0
Status byte CH1_S0, Byte 0
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
RegCom
General
Error
Wire
Break
–
User Over-
range
User
Under-
range
Over-
range
Underrange
Underrange
Measurement range underflow
0:
The “Show measurement underrange” diagnosis is deactivated or the
temperature value or field-side input voltage is above the
temperature/voltage lower limit.
1:
The temperature value or field-side input voltage is below the
temperature/voltage lower limit.
Overrange
Measurement range overflow
0:
The “Show measurement overrange” diagnosis is deactivated or the
temperature value or field-side input voltage is below the
temperature/voltage upper limit.
1:
The temperature value or field-side input voltage is above the
temperature/voltage upper limit.
User
Underrange
User limiting value underrange
0:
The “Show underrange of user range values” diagnostics is deactivated or
the temperature value or field-side input voltage is above the user-defined
temperature/voltage lower limit.
1:
The temperature value or field-side input voltage is below the user-defined
temperature/voltage lower limit.
User Overrange
User limiting value overrange
0:
The “Show overrange of user range values” diagnostics is deactivated or
the temperature value or field-side input voltage is below the user-defined
temperature/voltage upper limit.
1:
The temperature value or field-side input voltage is above the user-defined
temperature/voltage upper limit.
Wire Break
Wire break
0:
The “Show wire break” diagnostic is deactivated or there is no wire break.
1:
“Show wire break” is activated and there is a wire break.
General Error
Group error
0:
There is no error or bit 0 (underrange), bit 1 (overrange) and bit 5 (wire
break) is/are not set.
1:
There is a general error; bit 0 (underrange), bit 1 (overrange) or bit 5 (wire
break) is set.
RegCom
Register communication
0:
Register communication is deactivated (normal mode).
1:
Register communication is enabled.