Process Image 41
750-458 8AI; TC; Adjust
Manual
Version 1.3.0
Table 28: Process Image Type C, ID8, Two's Complement Representation
Temperature
°C
Numeric value
Status
Byte
Hex.
Error
LED
Binary
Hex.
Dec.
---
'1000.0000.0000.0000'
0x8000
−32768
0x00
OFF
Range violation, cold
junction
< 0.0
'0000.0000.0000.0000'
0x0000
0
0x41
ON
Underrange
0.0
'0000.0000.0000.0000'
0x0000
0
0x00
OFF
100.0
'0000.0011.1110.1000'
0x03E8
1000
0x00
OFF
200.0
'0000.0111.1101.0000'
0x07D0
2000
0x00
OFF
300.0
'0000.1011.1011.1000'
0x0BB8
3000
0x00
OFF
400.0
'0000.1111.1010.0000'
0x0FA0
4000
0x00
OFF
500.0
'0001.0011.1000.1000'
0x1388
5000
0x00
OFF
1000.0
'0010.0111.0001.0000'
0x2710
10000
0x00
OFF
1500.0
'0011.1010.1001.1000'
0x3A98
15000
0x00
OFF
1700.0
'0100.0010.0110.1000'
0x4268
17000
0x00
OFF
1768.0
'0100.0101.0001.0000'
0x4510
17680
0x00
OFF
1800.0
'0100.0110.0101.0000'
0x4650
18000
0x00
OFF
1820.0
'0100.0111.0001.1000'
0x4718
18200
0x00
OFF
2000.0
'0100.1110.0010.0000'
0x4E20
20000
0x00
OFF
2315.0
'0101.1010.0110.1110'
0x5A6E
23150
0x00
OFF
Overrange
'0101.1010.0110.1110'
0x5A6E
23150
0x42
ON
> 2315.0
Wire break
'0111.1111.1111.1111'
0x7FFF
32767
0x60
ON
---