54 Use in Hazardous Environments
WAGO-I/O-SYSTEM 750
750-439 8DI NAMUR Ex i
Manual
Version 1.3.0, valid from HW Version 03, SW Version 03
Figure 25: Text Detail – Marking Example for Approved Ex i I/O Module According to NEC 505
Table 35: Description of Marking Example for Approved Ex i I/O Module According to NEC 505
Marking
Description
CI I,
Explosion protection group
Zn 2
Area of application
AEx
Explosion protection mark
nA
Type of protection
[ia Ga]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
Figure 26: Text Detail – Marking Example for Approved Ex i I/O Module According to NEC 506
Table 36: Description of Marking Example for Approved Ex i I/O Modules According to NEC 506
Marking
Description
CI I,
Explosion protection group
Zn 2
Area of application
AEx
Explosion protection mark
nA
Type of protection
[ia IIIC]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)