32 Device Description
WAGO-I/O-SYSTEM 750 XTR
750-404/040-003 Counter Adjust XTR
Manual
Version 1.1.0
Table 22: EMC – Immunity to Interference
Standard
Test Value
Line Frequency Disturbances
• EN 60255-26
To ensure proper function in the event of line
frequency disturbances in accordance with EN
61000-4-16 or EN 60255-26 “Line Frequency
Disturbance Variables” with respect to the
power supply, shielded cables must be used at
cable lengths of 10 m or more.
Alternating Components of the Voltage to DC Line Connections
• EN 61000-4-17
• EN 60255-26
15 %
Damped Oscillatory Waves
• EN 61000-4-18
• EN 60255-26
• IEEE C37.90.1
1.25 kV conductor/conductor
2.5 kV conductor/ground
Voltage Dips, Short-term Interruptions and Voltage Fluctuations to DC Supply
Inputs
• EN 61000-4-29
• EN 60255-26
Standard not applicable
Harmonics
• Shipbuilding
*)
Standard not applicable
*)
The list of ship certifications issued is available in the section “Approvals”.
When used in power plants and high/medium voltage substations, the maximum
length of the field supply cables is limited to 2 m (unshielded cables) or 10 m
(shielded cables).