0787-1212
Properties
22
Product manual | Version: 1.0.0
Compact Power Supply
Table 19: Technical Data – Product Protection
Property
Value
1
Used only as an AC fuse. An external DC fuse must be used with DC supply (see
8
).
2)
Internal limitation via a second control loop, deactivation of power supply, automatic restart
3)
The user must ensure that the voltage is not exceeded for power feedback.
4)
Shutdown, automatic restart
3.7.8 Safety
Table 20: Technical Data – Safety
Property
Value
Safety transformer
According to EN 61558-2-16
Input and output insulation,
per EN 62368-1
SELV/PELV
Protection class, with protective wire connection
I
Leakage current, max.
1)
≤ 0.25 mA
Insulation resistance, input to output, min.
2)
≥ 100 MΩ/500 VDC
Dielectric strength (input – output)
3)
3000 VAC
1)
For power at 230 VAC
2)
at 25 °C and 75 % RH
3)
Type testing / 60 s
3.8 Approvals
The following approvals have been granted for the product:
Table 21: Approvals
Logo
Approval
Standard
CE Conformity Marking
UL 508
UL 60950-1
Note
More information on approvals
You can find detailed information on the approvals online at:
ü
number>
3.9 Standards
The product meets the following standards:
Table 22: Standards: Mechanical and Climatic Environmental Conditions
Standard
Test Value
Mechanical Environmental Conditions
EN 60068-2-6
f = 5 …150 Hz: 1g, 3.5 m
IEC 60068-2-27 shock
15g, 11 ms, 6 shocks per axis and direction, half-sine
EN 61131-2, sec. 4.3
Freefall ≤ 300 mm (packaged in the product packaging)