2789-9023
Fieldbus Description
Product manual | Version: 1.0.0
37
EtherNet/IP Communication Module
Attribute
ID
Access
Data type Description
Value Limits
Factory setting
Min. Max.
240
Get/Set
UINT16
Enables BroadcastStormProtection (0 =
off, 1 = on)
0
0
1
Switch Settings for Channel 2
Table 40: Internal Module Parameters – Switch Settings for Channel 2
Attribute
ID
Access
Data type Description
Value Limits
Factory setting
Min. Max.
248
Get/Set
UINT16
Enables “Autonegotiation” mode (0 =
off, 1 = on)
1
0
1
249
Get/Set
UINT16
Forces 100 MB connection
(0 = off, 1 = on)
1
0
1
250
Get/Set
UINT16
Forces full duplex connection (0 = off, 1
= on)
1
0
1
252
Get/Set
UINT16
Enables BroadcastStormProtection (0 =
off, 1 = on)
0
0
1
Note
Restart after adjusting switch and ETHERNET settings!
After settings are modified on this page, the product must be restarted with
[Reboot
Module]
or by power cycling
1)
it.
1) The device must be disconnected from the supply voltage for at least five seconds.
Date
Table 41: Internal Module Parameters – Date
Attribute
ID
Access
Data type
Description Value Limits
Factory setting
Min.
Max.
260
Get/Set
UINT8
Year
0
0
99
Get/Set
UINT8
Month
1
1
12
Get/Set
UINT8
Day
1
1
31