SinePower
Connecting the inverter
47
10.2
Connecting the inverter to the battery
A
NOTICE!
Do not reverse the polarity. Reversing the polarity of the battery
connections will cause a great spark and the internal fuses will
melt. The fuses should only be replaced by an electrician!
I
NOTE
Tighten the nuts and bolts to a torque of 12 – 13 Nm. Loose con-
nections may cause overheating.
➤
Set the main switch (fig.
2
1, page 4) to “Off”.
➤
Unscrew the four fastening screws (fig.
8
2, page 7) from the back side
of the device with the included hexagon socket wrench.
➤
Take off the hood (fig.
8
1, page 7).
➤
Guide the plus cable through the “POS (+)” opening and the minus cable
through the “NEG (–)” opening in the hood.
➤
Loosen the safety bolt slightly(fig.
8
3, page 7).
➤
Push the cable lug (fig.
8
5, page 7) of the positive cable between the
spring washer (fig.
8
4, page 7) and the positive terminal (fig.
8
6,
page 7).
➤
Screw the safety bolt back in.
➤
Connect the negative cable to the negative terminal (fig.
8
7, page 7).
➤
Connect the earth terminal (fig.
3
5, page 4) to the chassis with a cable
having a diameter of at least 16 mm².
➤
Replace the hood of the device and tighten the screws.
➤
Lay the positive cable from the inverter to the positive terminal of the ve-
hicle battery and connect it there.
➤
Lay the negative cable from the inverter to the negative terminal of the ve-
hicle battery and connect it there.
10.3
Connecting the 230 V power cable
➤
Connect the 230 V
w
connection cable with safety coupling (fig.
1
3,
page 3) to the 230V
w
output jack (fig.
3
3, page 4).
➤
Connect the safety plug to the 230 V
w
mains