AirConServiceCenter
Troubleshooting
The display shows
“Error 12”
It was not possible to remove
any refrigerant from the inter-
nal tank during the software
test.
Check pressure transducer
calibration. Check whether
the tank valve on the internal
tank is open. Check the RE
valve. Is the ambient temper-
ature below 10 °C?
The display shows
“Error 60”
During the hybrid service
(flushing the service hoses
with hybrid oil), a vacuum
could not be achieved.
Are the service hoses con-
nected to the hybrid flush
container? Is the hybrid flush
container fitted the right way
round? Check the connec-
tions for leaks.
The display shows
“Error 61”
Pressure increase during the
hybrid service (flushing the
service hoses with hybrid oil).
Are the service hoses con-
nected to the hybrid flush
container? Is the hybrid flush
container fitted the right way
round? Are the service cou-
plings open?
Fault
Cause
Remedy
Summary of Contents for AirConServiceCenter ASC1000
Page 2: ......
Page 218: ...RU AirConServiceCenter 218 2 3 405 C R 134a...
Page 219: ...RU 219 AirConServiceCenter 2 4 TRG 402 AirConServiceCenter...
Page 220: ...RU AirConServiceCenter 220 2 5 AirConServiceCenter 230 50 2 6...
Page 233: ...RU 233 AirConServiceCenter 6 10 ASC2000RPA I 1 12 2 8 3 12 AirConServiceCenter 8...
Page 238: ...RU AirConServiceCenter 238 I 7 2 2 1 STOP Enter user code Wrong code Max Mustermann...
Page 251: ...RU 251 AirConServiceCenter 8 Process start ENTER 9 D 10 E 11 15 D D E...
Page 259: ...RU 259 AirConServiceCenter 9 9 1 A 9 2 9 3 AirConServiceCenter WAECO...
Page 263: ...RU 263 AirConServiceCenter Error 11 Error 12 10 C Error 60 Error 61...
Page 267: ...RU 267 AirConServiceCenter...