Operation
HI 400HD D / HD G
36
ghi_tx001462gb.fm
4.18
Connecting Power to the Machine (Preheating)
Requirements
Power source (115VAC)
Machine properly positioned
Operation mode switch in the OFF (0) position
]
Extension
cords
Restrictions for extension cords:
Use only 3-wire type extension cords with heavy-duty plugs.
The maximum length of extension cord usage per circuit is 30 m (100 ft).
Use 12-gauge extension cords for lengths up to 15 m (50 ft).
Use 10-gauge extension cords for lengths up to 30 m (100 ft).
Procedure
Perform the procedure below to connect power to the machine.
1. Verify that the operation mode switch is in the OFF (0) position.
2. Connect the main power cord cord to a properly-rated power source.
Note: If the ambient temperature is below freezing, wait 10–30 minutes before pro-
ceeding.
Result
Power has now been connected. The machine is ready for pre-starting checks.
WARNING
Fire hazard and electric shock hazard. The use of under-sized extension cords can
lead to fire and electric shock. Fire and electric shock can cause severe injury.
f
Do not use under-sized extension cords.
CAUTION
Burn hazard. The self-regulating fuel heater, located inside the fuel filter canister,
will initiate when power is connected to the machine. The surface of the fuel filter
canister may become very hot.
f
Use caution when working with the fuel filter canister.