Troubleshooting Voltage Issues
GV Generators
wc_tx000772gb.fm
18
Continued from the previous page.
4. Check each winding to ground. Measure the resistance between each post
where the yellow (Y), red (R), black (B), and green (G) wires were connected
and the ground stud.
Is any resistance measured for any of the checks?
Result
The procedure to check the stator windings is now complete.
Reassemble the generator or, if the problem has not been resolved, continue with
the next topic.
Yes ____
No ____
The stator windings have failed. Replace the stator.
Continue.