132
Mobile Generator
How to Connect Loads (600V)
12.8
Connecting 600V, 3-Phase Loads
1. Stop the engine and turn the main circuit breaker off.
2. Turn the voltage selector switch to the 600 position.
3. Open the lug door and connect the wires from the load as shown.
4. Close the lug door.
5. Start the machine and fine-tune the voltage as necessary using the voltage
adjustment rheostat.
WARNING
Electric shock hazard. High voltage can cause serious injury or death.
►
Connections must be made by a qualified electrician.
600V
208/240V 3
Ø
120/139V 1
Ø
wc_gr011356
600V 3Ø
600 P3
24
60
100% 175 0
13
HOT HOT HOT
GN
600V 3Ø
TRANSFORMER
HOT HOT HOT
GN
WH
600V
600V
600V 3Ø
346V
346V
346V
600V
1Ø
120/240V
3Ø
277/480V
3Ø
transformateur
transformador
Summary of Contents for G 25
Page 1: ...5200015081 04 0215 5 2 0 0 0 1 5 0 8 1 Operator s Manual Mobile Generator G 25 T4i G 25 T4f EN...
Page 6: ...Foreword 6 wc_tx003565gb_FM10 fm Notes...
Page 165: ...wc_tx003641gb_FM10 fm 165 G 25 Maintenance Tier 4i Engines Isuzu 770012...
Page 168: ...wc_tx003642gb_FM10 fm 168 Maintenance Tier 4f Engines Isuzu 770006...
Page 169: ...wc_tx003642gb_FM10 fm 169 Maintenance Tier 4f Engines Isuzu 770007...
Page 170: ...wc_tx003642gb_FM10 fm 170 Maintenance Tier 4f Engines Isuzu 770008 770009...
Page 171: ...wc_tx003642gb_FM10 fm 171 Maintenance Tier 4f Engines Isuzu 770010...
Page 191: ...wc_tx003111gb_FM10 fm 191 User s Information for Transport Canada Fuel Tank...
Page 192: ...wc_tx003111gb_FM10 fm 192 User s Information for Transport Canada Fuel Tank...
Page 212: ...Schematics Machines with Deep Sea Controller G 25 212 Notes...
Page 213: ......