8
-
be isolated from the gas supply piping system by closing its individual manual shut-off
valve during any pressure testing of the system.
Prior to lighting, check all joints in the gas supply line for leaks.
Use soap and water solution. Do not use an open flame.
GAS PRESSURE REGULATOR INSTALLATION
Gas regulator pressure is preset at 5” Water Column (W.C.) for natural gas, and 10” W.C.
for propane gas. Minor adjustments may be required based on site specific gas pressure.
Install the regulator as close to the broiler on the gas supply line as possible. Make sure
that the arrow on the underside of the regulator is oriented in the direction of gas flow to
the broiler (Fig. 7) and the regulator is positioned with the vent plug and adjustment
screw upright (Fig. 8).
Fig. 7
Fig. 8
The supply pressure (upstream of the regulator) should be 7-9” W.C. for natural gas and
11-12” W.C. for propane gas. At no time should the charbroiler be connected to supply
pressure greater than ½ psig (3.45 kPa) or 14” W.C.
CASTER EQUIPPED CHARBROILERS
Charbroilers mounted on stands with casters must use a
flexible connector (not supplied) that complies with the
Standard for Connectors for Movable Gas Appliances,
ANSI Z21.69 • CSA 6.16 and a quick-disconnect device
that complies with the Standard for Quick-Disconnect
Devices for use With Gas Fuel, ANSI-Z21.41 • CSA 6.9.
In addition, adequate means must be provided to limit
movement of the broiler without depending on the
connector and the quick-disconnect device or its
associated piping to limit broiler movement. Attach the
restraining device at the rear of the charbroiler. If
disconnection of the restraint is necessary, turn off the
gas supply before disconnection. Reconnect the restraint
prior to turning the gas supply on and return the
charbroiler to its installation position.
Connect Gas Line
Strain Relief Here
Fig. 9
Charbroilers mounted on stands with casters
must use a flexible connector (not supplied) that
complies with the Standard for Connectors for
Movable Gas Appliances, ANSI Z21.69 • CSA
6.16 and a quick-disconnect device that complies
with the Standard for Quick-Disconnect Devices
for use With Gas Fuel, ANSI-Z21.41 • CSA 6.9.
In addition, adequate means must be provided to
limit movement of the broiler without depending
on the connector and the quick-disconnect device
or its associated piping to limit broiler movement.
Attach the restraining device at the rear of the
charbroiler. If disconnection of the restraint is
necessary, turn off the gas supply before
disconnection. Reconnect the restraint prior to
turning the gas supply on and return the
charbroiler to its installation position.