Electric Steamers
MODEL
TOTAL KW
AMPERAGE
1 PHASE
3 PHASE
3 PHASE - 4 WIRE
208V
240V
208V
240V
480V
220/380V and
240/415V
VSX24E
24*
116
100
67
58
29
34
VSX36E
24*
67
58
29
34
36
100
878
44
50
42
117
48
116
58
67
VSX42ET
24*
67
58
29
34
36
100
87
44
50
*Standard
Steam Supply
Dry steam must be provided to the steamer. If the
steam is heavy with condensate, a ball float trap must
be used in the line and plumbed in before the pressure
reducing valve. To ensure rapid heat up of heavy cold
loads, the steam supply line must be sized to maintain
pressure as outlined below.
DIRECT STEAM STEAMERS
(POTABLE)
REGENERATED STEAM
STEAMERS (*NON-POTABLE)
Supply Pressure
15 psi (max.)
15 psi (max.)
Flow Rate
100 lb. per hour total (min.)
125 lb. per hour total (min.)
Pressure Reducing Valve Output
10 psi (furnished)
set accordingly for good steam
generation but no higher than 15 psi.
(furnished)
*Potable steam is not required for regenerated models but could be used.
Water Supply
Supply pressure should be
20-80 psig
In line strainer for supply line
(Not Supplied)
VSX BOILER BASE SERIES CONVECTION STEAMERS - GENERAL