background image

MECHANICAL

Exterior Dimensions:
Model

A

B

C

D

A-130

510mm(20.0")

350mm(13.8")

290mm(11.5")

330mm(13.0")

A-550

635mm(25")

410mm(16.0")

 400mm(15.8")

430mm(17.0")

A-1750

815mm(32")

545mm(21.5")

 610mm(24")

 535mm(21")

Internal Muffle Dimensions:
Model

E

F

G

A-130

120mm(4.6")

140mm(5.7")

 130mm(5.2")

A-550

180mm(7.0")

 230mm(9.0")

230mm(9.0")

A-1750

250mm(10.0")

360mm(14.0")

320mm(12.5")

Model

Furnace Weight:

 Shipping Weight:

A-130

12kg(26lbs)

15kg(32lbs)

A-550

20kg(45lbs)

25kg(54lbs)

A-1750

44kg(97lbs)

60kg(132lbs)

8

5

  OPERATIONS

STARTING OPERATION:
Close the furnace door.  Turn the green power switch to the on (I) posi-
tion.  The light inside the switch will turn on.  An interlock door switch
located inside the furnace disconnects the power to the muffle when the
door is opened.  The door must be closed for the furnace to heat.

Turn the setpoint knob to desired temperature and the furnace will ramp
to the set temperature.  Turn off the power switch, to turn off the furnace.

The temperature rate will start out at full speed and gradually slow as it
approaches the setpoint temperature.  If a slower temperature increase
rate is required set the temperature at several intermediate temperatures.
This will cause the control to approach each intermediate temperature at
a slower rate.

Note: Observe the rate curves on Pg.6-7 to determine the time required

to reach set-point.

OPERATING EXAMPLES:
The furnace will continuously operate at 900°C each day.

- Insert work, close door, adjust knob to 900°C (white inside scale).
- Turn power switch to on position (green light should come on when

door is down).  If the same temperature is needed each day the knob
does not have to be adjusted.

- The furnace will heat to the temperature indicated on the front control

panel.  Turn off the power switch when the cycle is finished.

A temperature cycle calls for a slow ramp to 700°C (1300°F).
Procedure:

- Insert work and close door.
- Turn power switch to on position (green light should come on when

door is down).

- Turn the set-point knob to 300°C (inside scale), 30 minutes later turn

the knob to 500°C, and finally 30 minutes later to 700°C .

- The furnace load slowly heats to the desired 700°C.

Note: Because of the nature of the control, the first 90% of the rate will

be relatively fast while the last 10% takes somewhat longer.  The
furnace will reach the set point, but it takes some time.  If a faster
rate is required, set the furnace to approximately 10 to 20% higher
than desired set-point and then adjust to the desired set-point when
temperature is reached.

OUTLINE DRAWINGS mm(in)

A

B

D

C

E

F

G

Summary of Contents for A-130

Page 1: ...e facts upon which such a claim is based Failure of the buyer to give written notice of such a claim within this time period shall be deemed to be a waiver of such claim DISCLAIMER Theprovisionshere instatedDegussa Ney soleobliga tion and exclude all other remedies or warranties expressed or implied including those related to MERCHANTABILITY and FITNESS FOR A PARTICULARPURPOSE LIMITATION OF LIABIL...

Page 2: ...rvice the furnace Do not attempt to service the furnace until you read and understand the service manual See Service Manual under Accessories on page 11 Do not operate the furnace controls with tongs or other tools the tongs will damage the control switches Do not use solvents or liquid cleaners on the control panel they will enter the panel and damage it Do not place firing trays or other hot obj...

Page 3: ...mperature Check the fuse on the controller PCB Check heating element plates for continuity If muffle is hot but the meter reads a low temperature check the thermocouple for shorts to the cabinet The control will slowly approach the setpoint temperature Set to a higher temp and then turn down to reduce the heatup time On the low voltage model 100 125VAC the heating element plates are wired in paral...

Page 4: ...located at least 15cm 6 away from walls shelves and heat sensitive materials Open the furnace door and remove the packing material from inside the furnace NOTE The furnace front panel will show some discoloration around the muffle due to the calibration and burnin cycles performed at the factory 2 The furnace should not be located directly under shelves and other airflow restrictions 3 On high vol...

Page 5: ...l cause the control to approach each intermediate temperature at a slower rate Note Observe the rate curves on Pg 6 7 to determine the time required to reach set point OPERATING EXAMPLES The furnace will continuously operate at 900 C each day Insert work close door adjust knob to 900 C white inside scale Turn power switch to on position green light should come on when door is down If the same temp...

Page 6: ...600 C 1000 C 1200 C 400 C 200 C 0 10 20 30 40 50 60 TIME minutes 70 90 110 0 C Cool Down Door Closed Cool Down Door Open Test Conditions nominal line voltage no load in the muffle control set to 1100 C Lower temperatures will require approximately the same amount of heating time due to the nature of the control Setting the control higher than the desired setpoint and then reducing it will shorten ...

Reviews: