Table 4. Recommended cycle rate (CPH).

SYSTEM

CPH SETTING

Steam Gravity

1

Hydronic heat

3

Gas or Oil forced air

6

Electric heat

9

Note: If the equipment manufacture recommends
a different rate use the rate specified by the
equipment manufacture.

Setting Heating Cycle Rate. (OP:03)

In cooling, the cycle rate is fixed at 4 Cycles per
hour. To set the cycle rate in heating; while in
installer setup,

a.

 

Press 

∆ 

key, the display will

show the heat cycle rate.

b. Press

 

∇ 

key to change the heat

cycle rate to 1,3,4,5,6,9 or 12
cycles per hour.

Note: The default is set at 6 cycle per hour.
Table 4 is the recommended cycle rate. The
installer should consult with the heating
equipment manufacturer for proper use.

Setting cooling algorithm. (OP:04)

The cooling algorithm can be selected as normal or
aggressive. For aggressive, the system will cool down
the room to setting point faster than normal algorithm.
However, an overshoot might be occurred in some
situations.

a. Press 

∆ 

key to show the cooling

algorithm.

b. Press 

∇ 

key to change algorithm.

  0 = Normal algorithm (default).
  1 = Aggressive algorithm.

Setting Cooling Delay Time. (OP:05)

In some applications, there is a necessity to delay the
operation of the cooling equipment for protection
purposes. While in the installer setup,

a.

 

Press 

∆ 

key. The display will

show cooling delay time.

b.

 

Press 

∇ 

key to select the cooling

delay time (0,3,5 minutes).

NOTE : The default setting is  3
minutes.

Temperature offset. (OP:06)

The temperature can be offset from +3 to -4 

°

F to

eliminate the effect of installing location (e.g. direct
sunlight). The thermostat will indicate room
temperature by using actual reading plus (or minus )
the offset value.

a. Press 

∆ 

key to show temperature

offset.

b. Press 

∇ 

key to select offset

value (default = -1 

°

F).

NOTE : The default setting is  -1 

°

F.

Summary of Contents for TE80SB

Page 1: ...le 1 Description of Thermostat Model Mounting System Selection Fan Selection Powering Method Backlight TE80SB VERTICAL COOL OFF HEAT ON AUTO Power Stealing Backlight Fig 1 Thermostat FEATURES 7 Day pr...

Page 2: ...d 1 5 Amp continuous 0 02 to 1 5 A continuous 0 02 to 1 5 A continuous 0 02 to 0 5 A continuous TEMPERATURE RATINGS Temperature setting range Ambient temperature range Shipping temperature range 40 to...

Page 3: ...as indicated will result in poor temperature control NOTE Level thermostat mounting is for appearance only and is not required for proper thermostat operation Mounting Thermostat Take out the back pl...

Page 4: ...s used may result in the overheating of the electric heater elements due to improper fan operation The set up switch is an internal switch E F located near the wiring terminals It is used to select pr...

Page 5: ...the following steps to change each of the settings Each time you press key you will advance to the next operating parameter To go back you must re enter the installer set up as described above INSTALL...

Page 6: ...l or aggressive For aggressive the system will cool down the room to setting point faster than normal algorithm However an overshoot might be occurred in some situations a Press key to show the coolin...

Page 7: ...tarts and stop with heating equipment Minimum Off Timer For cooling when the thermostat calls for operation while the minimum off timer is not expired the star symbol keeps flashing Back Lighting The...

Page 8: ...e Note Default setting can be restored to memory by pressing HOLD and RUN buttons at the same time for 3 seconds Press or key to select desired programming period as below Press PROG to proceed The th...

Page 9: ...isappeared Set point will be updated to the programmed data Note that only the HOLD button can be used to exit the HOLD temperature CLOCK ADJUSTMENT The clock needs to be adjusted when installed The c...

Page 10: ...HEAT B terminal will get energized 2 Press key until the set point is higher than room temperature The star symbol is shown on the display The heating equipment is on and terminal W is energized 3 Pre...

Page 11: ...Note that resistor has to be installed at the fan terminals and not at thermostat terminals To install the Resistor 1 Disconnect power supply 2 Connect the resistor leads to the terminals as shown in...

Reviews: