The charging regulations of the battery manufacturer are absolutely to be observed!
An operation of the unit at a LiFePO4 battery without BMS Battery Management System and
without equalization charging of the cells (balancing) as well as safety circuit is not admissible!
The battery temperature sensor must be installed at the battery (screw to the negative pole)
and must be connected at the unit. It serves as protection for the battery.
No function without temperature sensor, LED
"Main Charge" is flashing
!
If possible, the battery temperature should be kept above 0 °C.
6
"LiFePO4 14.2 V"
Switch Position
U1=14.20 V U2=13.60 V
0,5 h
Adapted to
Victron LFP-BMS 12,8
TransWatt TH 12/xxx
of the indicated capacity rates.
Operation of the battery only with own BMS
and prescribed safety circuit!
7
"LiFePO4 14.4 V"
Switch Position
U1=14.40 V U2=13.80 V
0.3-1 h
Adapted to
MT Büttner Elektronik MT-Li - Series
of the indicated capacity rates, types with integrated
safety circuit and integrated BMS.
Super B SB12VxxE
GNB/Exide SL12 xxxHC with BMS
of the indicated capacity rates. Operation only with
own BMS and prescribed safety
circuit!
8
"LiFePO4 14.6 V"
Switch Position
U1=14.60 V U2=13.80 V
0,3 h
Adapted to
Super B SB12Vxx - M (Epsilon)
RELION Types "RB"
of the indicated capacity rates, types with integrated
safety circuit and integrated BMS.
Operation of other batteries only with own BMS
and prescribed safety circuit!