background image

 

- 11 - 

Start-up and Function Test:

 

After connection of the charging converter according to the description, a function test can be executed. 
1.

 

Start the vehicle or switch on ignition (Kl.15).  

-

 

The charging converter will be activated and starts with 10 % of the maximum charging capacity. 

-

 

The LEDs "Power”, "Battery I”, "Main Charging” will be lighting, LED "Current” is lighting dimly. 

2.

 

Increase the speed of the vehicle to increase the voltage at the starter battery until it exceeds the adjusted value for 

the increase of the charging capacity. 

-

 

The charging capacity will be increased and is raised to the maximum value or to the required value of the 

charging characteristic line, if the board battery is already full.  

-

 

The lighting intensity of the LED "Current" will be reduced or increased depending on the charging current. 

 

Function of the Power Control for Starter Battery and Generator: 

The charging converter is activated by the control input "Kl.15 / D+", and will be deactivated automatically if the motor is 

switched-off. It starts with 10 % of its achievable charging capacity. 
The setting of the two slide switches "Input Type" on the unit's rear (see table 2) now affects the further load of the 

starter battery circuit supplying current to the charging converter.  
After the motor start, also the starter battery shall be charged immediately and its starting capacity shall be maintained. 

Therefore, the gradual increase of the charging capacity for the board battery will not be effected before the voltage 

value "increase of the charging capacity" of the starter battery is reached. 
In case of strong load on the starter circuit due to many large consumer loads and the starter battery’s voltage drops 

below the value "reduction of the charging capacity", such as during motor idling, there will be a gradual reduction of the 

charging capacity for the battery Board I, to relieve the starter circuit. But the minimum charging capacity will always be 

10 % of the achievable charging capacity. 
If the voltage drops below the "Switching off threshold charging converter" for 30 sec., the charging converter will be 

switched-off automatically. As soon as the voltage exceeds the threshold "increase of the charging capacity", the 

converter will be switched-on, and the capacity will be increased gradually until the required (maximum) charging 

capacity is reached. 
A reduction of the charging capacity by more than 30 % due to insufficient input voltage of the generator will be indicated 

by a flashing LED "Batt. II". The LED will turn off, as soon as the input voltage is sufficient or when the power requirement 

had dropped anyway due to a charged board battery "I". 

 

 

Pilot Lamps: 

 

"Battery Full" 

(Board battery fully charged,

 green

):

 

 

If it is on: 

Battery has been charged to 100 %, trickle charge U2 and storage charge U3, finished. 

 

If it is flashing:  Main charging process is effected in the charging phase U1, indication of charging state of 

 

 

approx. 90 % (short flashing), gradual increase to 100 % (long flashing). 

 

Off: 

Main charging process is still effected in the charging phase I. 

 

"Main Charging" 

(Main charging board battery, 

yellow

):

 

 

If it is on: 

Main charging process is effected in the phase I and after that in the charging phase U1. 

 

Off: 

Trickle charge U2, U3. 

 

If it is flashing:  1.  Battery temperature sensor is not connected! 

 

2.  External battery overvoltage  

>15 V 

   

delay 20 sec., 

 

 

 

  Automatic reset  

<13.2 V (depending on type),  

delay 30 sec. 

 

"Current"

 (Charging Current,

 red

):

 

 

The lighting intensity will be 

reduced or increased depending on the supplied charging current

Turns off < 0.2 A. 

 

"Battery I" (

Board battery,

 yellow

):

 

 

If it is on: 

Control and charging of board battery "I". 

 

Off: 

Board battery "I" is separated from the charging converter (safety switch). 

 

If it is flashing:  Battery protection: Abnormal battery temperature < -20 °C or > 50 °C. Switchover to low safety 

charging voltage and half of the max. charging current. Automatic return at normal 

temperatures. 

 

Turns off 

Is lighting longer with turns off shortly approx. every 2 sec.: Battery temperature below 0 °C, the 

  shortly:  

charging current can be reduced for battery protection, and longer charging times can be 

expected, if the battery is discharged. 

Summary of Contents for VCC 1212-25 Li

Page 1: ...ery EURO Standard 6 6 plus vehicles information see page 10 table 2 switch position D Battery Port and Charging Programs Charging Port OUT Board battery supply battery depending on battery type and battery manufacturer 4 charging programs selectable adapted to Lithium LiFePO4 batteries see table 1 page 8 Further Characteristics of the Unit The charging voltage is free from peaks and is controlled ...

Page 2: ... lay 12 V 24V cables and 230 V mains supply cables into the same cable conduit empty conduit Check live cables or leads periodically for insulation faults points of break or loosened connections Occurring defects must be remedied immediately The unit is to be disconnected from any connection prior to execution of electrically welding or work on the electric system If the non commercial end user is...

Page 3: ...ctly from the positive pole of the board battery to the terminal Sense Out Recommended in case of a cable length of less than 2 m The terminal Sense Out can be left free 2 For battery temperature control connect the terminals TT Temp Sensor to the delivered temperature sensor Temperature Sensor page7 Input Side 3 Connect the vehicle s starter battery to the large terminals Battery II IN and observ...

Page 4: ...ill result in serious damage of the unit Input and output side of the charging converter are separated by galvanic isolation i e there is no conductive connection between the input II START side and the output I side BOARD Thus the two battery circuits are completely independent of each other and a mutual influence or disturbance is avoided Therefore the minus terminals I and II must imperatively ...

Page 5: ...3 0 6 5 m 30 bis 5 0 m 80 1 5 3 5 m 50 16 mm 2 bis 8 0 m 80 3 0 5 0 m 50 VCC 2412 25 Li VCC 2412 45 Li cross section Pole cable length IN II Motor Batt Fuse A cable length OUT I Main Batt Fuse A cable length IN II Motor Batt Sich A cable length OUT I Main Batt Fuse A 4 mm 0 5 2 0 m 30 6 mm 2 bis 11 0 m 30 1 5 3 5 m 30 0 5 2 0 m 50 10 mm 2 bis 18 0 m 30 3 0 6 5 m 30 bis 10 0 m 40 1 5 3 5 m 50 16 mm...

Page 6: ...e sensor had been connected The temperature sensor must be screwed down to the negative pole of the battery If possible the unit should always be installed as close as possible to the board battery I Observe the cable cross sections and lengths according to the table on page 5 Possibly existing cables which do not have the required cross sections must be adapted to the minimum requirements in any ...

Page 7: ...charging will be resumed as soon as the battery temperatures are normal After more than 10 hours overtemperature of 50 C a forced disconnection of the unit will be effected for reasons of safety Below 0 C the charging current will be reduced more strongly for battery protection and longer charging times can be expected The unit recognizes automatically a missing sensor cable break or short circuit...

Page 8: ...HC with BMS Operation only with own BMS Observe the battery capacity and the safety circuit U1 Main Full Charging 14 40 V 0 3 1 h U2 Full Trickle Storage Charging 13 80 V Continuous 3 LiFePO4 Charging program IU1oU2oU3 for make Victron LFP BMS 12 8 as well as make TransWatt TH 12 xxx Operation only with own BMS Observe the battery capacity and the safety circuit U1 Main Full Charging 14 20 V 0 5 h...

Page 9: ...LION RB100SC or LiFePO4 batteries with high charging voltage Imperatively observe the charging regulations and capacity rates of the manufacturer Switch Position Charging program 2 LiFePO4 IU1oU2 Adapted to Super B SB12VxxE GNB Exide SL12 xxxHC with BMS of the indicated capacity rates Switch Position Charging Program 3 LiFePO4 IU1oU2oU3 Adapted to Victron LFP BMS 12 8 TransWatt TH 12 xxx of the in...

Page 10: ...ly laid line Sense In is not required A wire jumper must be laid from IN to Sense In Note A continuous signal at Kl 15 D without running motor might discharge the starter battery Increase of the charging capacity 13 40 V 26 8 V Reduction of the charging capacity 12 80 V 25 6 V Switching off threshold charging converter 12 20 V 24 4 V 30 sec D Vehicles according to EURO Standard 6 6 and for paralle...

Page 11: ...rging capacity If the voltage drops below the Switching off threshold charging converter for 30 sec the charging converter will be switched off automatically As soon as the voltage exceeds the threshold increase of the charging capacity the converter will be switched on and the capacity will be increased gradually until the required maximum charging capacity is reached A reduction of the charging ...

Page 12: ...ard battery I OUT Charging converters protect themselves against connection of excessive battery voltage rates or they are switched off in case of defective additional charging systems solar systems generators etc switching threshold 15 5 V 31 0 V delay 20 s Reset by battery 12 75 V 25 5 V or by disconnection of the control signal D or Kl 15 Input overvoltage protection at the starter battery II I...

Page 13: ...g phase U1 4 During the phase U1 full charging cell equalization charging LED Main Charging is lighting the battery voltage will be kept constant on a high level The green LED Battery Full is flashing at first short flashing with rising charge increasingly longer flashing and gentle charging of the additional high battery capacity The charging converter controls the charging time as well as the ch...

Page 14: ...he voltage for the starter battery will not be displayed if the charging converter had been switched off In this case the terminal EBL START In is to be connected to the voltage of the starter battery If possible the unit should always be installed as close as possible to the board battery I Observe the cable cross sections lengths and fuses according to the table on page 5 Possibly existing cable...

Page 15: ...nnections Sense In and EBL Start In must be bridged to ensure that the starter battery will also be charged during mains charging mode Determined by the system the voltage of the starter battery will not be displayed correctly at the EVS during driving If possible the unit should always be installed as close as possible to the board battery I Observe the cable cross sections lengths and fuses acco...

Page 16: ...3 fold 3 fold Safety Protect ag Reverse Batt Short circuit Back Discharge Yes Yes Yes Yes Safety Timer per Charging Phase I U1 U2 Yes Yes Yes Yes EBL START In EVS Measuring Input Charging Port Yes Yes Charging Trickle Charging for Starter Battery 12 V 0 3 A 0 3 A Overcharge Protection Yes Yes Safety Protect ag Reverse Batt Short circuit Back Discharge Yes Yes Fitting Position of Unit any any any a...

Reviews: