13 -

 

Operating Instructions:

 

 

Display of the residual charging time: 

 

A flashing pilot lamp 

"Battery Full" 

allows conclusions concerning the progress of the charging phase U1 (full charging). 

Directly after the charging phase I (approx. 75 % for lead, approx. 90 % for LiFePO4), the pilot lamp will only be flashing 
momentarily. With progressing charging time, flashing will change more and more to permanent lighting, until the pilot 
lamp will be lighting most of the time and will only stop lighting for a short moment, shortly before 100 % full charge is 
reached.

 

 

Interruption of the charging process: 

In case of a power failure or withdrawal of the mains plug during the charging process, the charging process will be 
interrupted. The connected batteries will 

not 

be discharged by the charger. Thus, the charging process can be 

interrupted at any time. 
In case of frequent interruptions, particularly before reaching full charge (LED "Battery Full" is lighting 

permanently

), 

the battery should be subject to an 

occasional full charging cycle of 24 hours

 for equalization of the charge.

 

 

Overvoltage Protection: 

 

The unit protects itself against connection of excessive battery voltage rates or will be switched-off in case of defective 
additional charging systems (solar systems, generators or similar systems), switching threshold 15.5 V, delay 20 s.

 

Automatic charging is resumed, if the battery voltage drops to nominal level.  

 

Overvoltage Limitation:  

Charging voltage limitation to max. 15.0 V during all charging modes to protect sensitive consumers. 

 

Overload / Overheating Protection Charger: 

The charger is equipped with a double electronic protection against overload and protects itself against adverse 
installation conditions (e. g. insufficient ventilation, excessive ambient temperatures) by gradual reduction of the 
charging capacity. 

 

Lifetime of the battery:  Partially discharged lead batteries:

  

In contrast to other battery types, batteries on lead basis 

do not have any

 harmful memory effect. 

Consequently: In case of doubt, partially discharged batteries are to be 

charged fully 

as soon as possible.  

Store

 

only fully charged batteries

 and recharge them periodically, particularly in case of used (older) batteries and 

higher or lower temperatures.

 

 

 

Voltage Measurement: 

Measurement of the voltage is to be effected at the battery and never at the charger (loss at 

the charging cable).

 

 

 

 
 

Option:

  

Several Batteries at Main Charging Port I (Master): 

 

Parallel charging of two or several batteries of the same voltage (12 V) is admissible. The batteries are to be "paralleled", 
i. e. the "+" connections have to be coupled and should be connected to the "+" connection of the charger. The minus (-) 
connections have to be coupled in the same way. 

The total capacity (total Ah) should not exceed the indicated maximum 

battery capacity (depending on the case of application). 

According to the battery manufacturers, 

permanent

 parallel operation is admissible in case of two or several batteries of 

the same voltage, same type, same capacity, and of about the same age (history) in cross connection.

 

 

Summary of Contents for VAC 1215 M 3A

Page 1: ...f 50 80 which is advantageous for the battery lifetime Simultaneous floating of 12 V consumer loads such as alarm systems WLAN etc as well as the vehicle s starter battery see page 5 2 Main Battery II...

Page 2: ...nd hard mounting surface which is protected from moisture and humidity The unit can be installed in any position Protect the unit from aggressive battery gases Despite the charger s high efficiency he...

Page 3: ...3A VAC 1225 M3A VAC 1230 M 3A 2 5 mm 2 2x 3x 0 6 2 0 m 2x 3x 0 5 1 3 m 4 mm 2 2x 3x 1 5 3 2 m 2x 3x 0 8 2 0 m 2x 3x 0 6 1 6 m 2x 3x 0 5 1 3 m 6 mm 2 2x 3x 2 5 4 8 m 2x 3x 1 1 3 0 m 2x 3x 0 9 2 4 m 2x...

Page 4: ...tion For this purpose the temperature sensor measures the battery temperature In case of low temperatures winter operation the charging voltage will be increased in order to improve and accelerate ful...

Page 5: ...n in case inadvertently of power failure engine start higher charging of the battery batteries by the solar system high 12 V consumer current rates etc in the meantime Of course the temperature contro...

Page 6: ...for acid lead acid batteries acc to DIN 57 510 VDE 0510 for charging and trickle charging of supply board batteries Ensures short charging times high charging factor and acid mixing for open standard...

Page 7: ...attery manufacturer also recommended for batteries in round cell technology such as EXIDE MAXXIMA DC Charging Programs 5 8 9 for LiFePO4 Batteries 5 Charging characteristic lines charging voltage rate...

Page 8: ...d safety circuit and integrated BMS as well as Super B SB12Vxx E GNB Exide SL12 xxxHC with BMS of the indicated capacity rates Operation of the battery only with own BMS and prescribed safety circuit...

Page 9: ...he temperature equalization for battery I will also be applied to battery II Note If required the vehicle s starter battery is to be connected to the auxiliary port III 12 V 2 A 3A Charging program fo...

Page 10: ...longer and turns off shortly approx every 1 5 sec only with charging programs LiFePO4 Li battery protection battery temperature below 0 C the charging current might be reduced for protection of the Li...

Page 11: ...rmines the 100 full charge point of the battery for automatic switching to U2 In case of slightly discharged batteries the duration of phase U1 will be kept short for relief of the battery and low mai...

Page 12: ...tery has been deeply discharged In case of insufficient charging the charging process has been interrupted too often already during the charging phase I or U1 the charging process has not been complet...

Page 13: ...imitation Charging voltage limitation to max 15 0 V during all charging modes to protect sensitive consumers Overload Overheating Protection Charger The charger is equipped with a double electronic pr...

Page 14: ...g Phase I U1 U2 Yes Yes Yes Yes Lead Battery Regeneration at extended down time 2x week 1 h Yes Yes Yes Yes LiFePO4 Auto Wake Up in case of extended down time every 10 days 0 5 h Yes Yes Yes Yes or Li...

Page 15: ...y Never lay 12 V 24 V cables and 230 V mains supply cables into the same cable conduit empty conduit Check live cables or leads periodically for insulation faults points of break as well as loosened o...

Page 16: ...following standards or normative documents EN55014 1 EN55022 B EN 61000 3 2 EN 61000 3 3 EN61000 6 1 EN61000 4 2 EN61000 4 3 EN61000 4 4 EN61000 4 5 EN 61000 4 6 EN 61000 4 11 EN60335 EN50498 The prod...

Reviews: