18
•
The electrical connection is to be formed by recognised, specialist technicians,
authorised in terms of the current norm.
•
Make sure that the characteristics of the electricity supply conform to the indications.
•
It is mandatory to connect the equipment to an effective earth line.
The installation must include a device for disconnecting the equipment from the mains power supply. A protec-
tive fuse must also be installed, adequately sized and of a delayed type for starting motors. Attaching or hang-
ing any object from the ceiling fan's blades for any reason, is forbidden. This is because such actions could re-
sult in the machine being out of balance, with a resulting anomalous distribution of loads and consequences
such as the machine falling.
WARNING: SPECIFICALLY INSERT A SINGLE POWER SUPPLY LINE, FITTING A CLASS A TRIP
SWITCH IN THE LINE, IN ADDITION TO A PROTECTIVE CIRCUIT BREAKER IS OBLIGATORY.
INSTALLING THE CEILING FAN NEAR HIGH VOLTAGE LINES (GREATER THAN 1000 V AL-
TERNATING CURRENT OR 1500 V DIRECT CURRENT) IS EXPRESSLY FORBIDDEN.
6
OPERATION
6.1
Preliminary operations
Before starting the ceiling fan, check that:
1)
All electrical connections have been formed according to the instructions given
in this manual;
2)
The ceiling fan is free and clean;
6.2
Starting for the first time
Once assembly, installation and the electrical connection for the machine have been completed,
power the machine and wait for about 30 seconds to allow it to complete a self-diagnosis of its de-
fault parameters, and then start rotating. Subsequently, check that:
a. There is no imbalance in the installation due to incorrect assembly of components, or la-
tent defects in the same.
b. There are no metal noises or sounds coming from the machine itself.
c. The motor's diagnosis LED flashes every 2 seconds.
d. Rotation is clockwise, when looked at from below the ceiling fan.
6.3
Emergengy stoppage
In an emergency, switch off the power supply to the machine via the circuit breaker or the main power supply set
up. Warning! Do not touch the machine for a period of 5 minutes after switching off the power, because the
outside temperature of the machine may exceed 70°C.
6.4
Starting
The machine starts automatically as soon as electricity is supplied to it, after a delay of about 30 seconds to al-
low automatic setting of the operating parameters. To start the ceiling fan correctly, see the installation manual
enclosed with this manual. The fan speed is adjustable by a potentiometer standard supplied. The maximum
fan speed is indicated in the 8.1 Technical Data Table.
Summary of Contents for Nordik HVSL Super Blade
Page 23: ...23 Annex 1 Assembly Instructions...
Page 34: ...34 Assembly rod holder and rod PLACE ROD INTO MOTOR HOLDER AND FIX WITH SCREWS NUTS AND BOLTS...
Page 42: ...42 Tie Bar Kit...
Page 52: ...52 Electric connection...
Page 56: ...56 Fan line connection scheme...
Page 57: ...57 Existing plant wiring scheme...
Page 58: ...58 Multiwire system wiring Scheme...
Page 59: ...59...