23
Viewing status pages
With the unit ON, press the
buttons to view the status pages of each group. The infor-
mation can be viewed on each page / status group by pressing the
buttons.
The available screens:
SET time period and current period unlock display
On these screens, it is possible to:
- Use “Etb” to enable time period adjustment.
- Use “tb” to view the time period currently in progress (“—-” = no period active, “OFF” = OFF period active,
“COMF”= comfort period active, “ECO” = economy period active, “nIGH” = night period active, “H” = holiday
period active).
- Use “Set” to view and edit the set currently in use.
With time period adjustment, modification of the current set will be valid only for the current period.
FAN fan status display
On these screens, it is possible to view:
- The status (“—-” = fan disabled, “OFF” = fan off, “tOn” = fan awaiting start-up, “On” = fan on, “tOFF” = fan
awaiting shut-down).
- The status and speed of the supply fan, indicated with “SUP” and the return fan, indicated with the label
“rEt”.
ENGLISH
(MODE)
Summer/winter operation
(STC)
Set point for summer operation
(STH)
Set point for winter operation
(UO1)
Ambient humidity set point
(SCC)
Comfort period cold set point
(SCH)
Comfort period warm set point
(OEC)
Economy period cold offset
(OEH)
Economy period hot offset
(ONC)
Night period cold offset
(ONH)
Night period hot offset
(SDC)
Cold set point forcing from DI
(SDH)
Hot set point forcing from DI
(FSC)
Comfort period fans set point
(FSE)
Economy period fans set point
(FSN)
Night period fans set point
(BYN)
Display backlight mode
(BYU)
Display backlight percentage
(BYT)
Display backlight timeout
(BYU)
Cold set point forcing from DI
(BYT)
Hot set point forcing from DI
(PS1)
User password