Series S36 Instruction Manual
Chapter 3 Operation
3-11
800120
Energy Menu
–
For EMS Energy Meters Only
Password
ENTER
Use
keys to access menus
Energy
Menu
Loc in Sent
Flow
Yes or No
ENTER
Run Mode
Heating
System
Yes or No
% Returned
xxx
Configuration:
There are several possibilities regarding the measurement of water energy given the location of the
meter and the use of a second RTD. The table below summarizes the possibilities:
Fluid
Meter Location
Second RTD
Measurement
Water
“Sent” Flow Line
“Return Flow Line
Change in Energy
Water
“Return” Flow Line
“Sent” Flow Line
Change in Energy
Water
“Sent” Flow Line
None
Outgoing Energy
As above, you must properly configure the meter in the Energy Menu.
1.
Loc in Sent Flow? Select Yes or No based on where the meter is located. Refer to the above
table.
2.
Heating System? Select Yes for a hot water system used for heating. Select No for a chilled
water system used for cooling.
3.
% Returned. Select a number between 0% and 100%. Estimate the amount of water that
returns. It is usually 100% or can be less than 100% if historical data shows the amount of
makeup water used. If a second RTD is not used, set to 0%. When 0% is selected, the energy
calculation represents the outgoing energy only (no return energy is subtracted).
NOTE: the
meter ships from the factory assuming 0%.
Summary of Contents for SonoPro S36 Series
Page 44: ...Series S36 Instruction Manual Chapter 3 Operation 3 5 800120 Output Menu...
Page 92: ...Series S36 Instruction Manual Appendix A Specifications A 2 800120...
Page 96: ...Series S36 Instruction Manual Appendix C Sound Speed and Pipe Data C 2 800120 Pipe Chart...
Page 97: ...Series S36 Instruction Manual Appendix C Sound Speed and Pipe Data C 3 800120...
Page 98: ...Series S36 Instruction Manual Appendix C Sound Speed and Pipe Data C 4 800120...
Page 99: ...Series S36 Instruction Manual Appendix C Sound Speed and Pipe Data C 5 800120...
Page 100: ...Series S36 Instruction Manual Appendix C Sound Speed and Pipe Data C 6 800120...
Page 101: ...Series S36 Instruction Manual Appendix C Sound Speed and Pipe Data C 7 800120...
Page 102: ...Series S36 Instruction Manual Appendix C Sound Speed and Pipe Data C 8 800120...