Options are set by switches on the Chexit module. Before changing option settings, turn the Chexit off.
Changes in option settings take effect when the Chexit is turned on.

Seconds    Switch No. 1    Switch No. 2    Switch No. 3    Switch No. 4

0

2

4

6

8

10

12

14

16

18

20

22

24

26

28

 infinite

Rearm Time Switch Settings

off

on

off

on

off

on

off

on

off

on

off
on

off

on

off

on

off

off

on

on

off

off

on

on

off

off

on
on

off

off

on

on

off

off

off

off

on

on

on

on

off

off

off

off

on

on

on

on

off

off

off

off

off

off

off

off

on

on

on

on
on

on

on

on

Rearm Time Notes

1. Set the rearm time a few seconds longer than

the door will be open so the door closes before
the Chexit arms.

2. The Chexit is shipped from the factory with the

rearm time set to 10 seconds.

3. When the rearm time is infinite, the Chexit

arms when the door position switch detects
that the door is closed.

4. When the rearm time is infinite, you must open

and close the door after the Chexit is turned on.

5. If a door position switch is used, the Chexit

arms 2.5 seconds after the door closes.

6. If you are using a door position switch but you

want the full rearm time to expire before the
Chexit arms, call Von Duprin at 1-888-371-7331
and get instructions from Electrical Technical
Support.

7. For proper operation, the rearm time of each

ganged Chexit must differ by at least 2 seconds.

Location of Chexit

option switches

OPTIONS

Factory settings shown

8: Off
7: Off
6: Off
5: Off
4: Off
3: On
2: Off
1: On

Table 3. Chexit Options

Option

Rearm time

Nuisance delay

Nuisance alarm

Function

Switches Nos. 1 through 4 set amount of time you have to pass through door
after turning on key switch or using an external inhibit device (see table below)

If switch No. 5 is on, the pushpad must be pressed 2 seconds to set off alarm

If switch No. 6 is on, the Chexit horn sounds while pushpad is pressed during
nuisance delay; use in accordance with local code

Settings for Door No: ___

Self-test

Local fire alarm

If switch No. 7 is on, the Chexit performs a self-test when turned on; this
switch must be off for normal operation

If switch No. 8 is off, the Chexit internal horn sounds during a fire alarm

________ seconds

on                  off

on                  off

on                  off

on                  off

Summary of Contents for Chexit CX33A/35A

Page 1: ...ety and security needs as well as all requirements of NFPA101 for Special Locking Arrangement and UBC Special Egress Control Devices The Von Duprin Chexit device sounds an alarm and keeps an exit door secured for 15 seconds following an attempt to exit The Chexit releases immediately upon a fire alarm condition PUSH UNTIL ALARM SOUNDS DOOR CAN BE OPENED IN 15 SECONDS CX Rim Exit Device CX98 99 sho...

Page 2: ...onents you use in Table 1 3 Determine the physical location of each component used see Figure 1 4 Pull field wiring between component locations and frame side of power transfer see Figure 1 5 Mount components and connect them to field wiring see Figure 2 or Figure 3 6 Connect field wiring to frame side of power transfer Route wires through frame back box 7 Install frame back box and frame side of ...

Page 3: ...blue and brown wires separately Required Connect orange wire to white wire Connect green wire to white wire Use door loop or electric hinge Required Von Duprin PS873 Highly recommended Optional Required Optional wire multiple external inhibit devices in series Optional FIRE Used Yes Yes Table 1 Installation Components TYPICAL WIRING Figure 2 Wiring Connections Single Door Blue C Black GND Red 24 B...

Page 4: ... used rearms 2 seconds after closing and the unused door rearms after the full rearm time For proper operation the rearm times of ganged Chexits must differ by at least 2 seconds Double Door Application Wire Functions Power supply 24 VDC Common for NO output 24 VDC 1 A maximum Normally open output closes during alarm Communication line used to connect Chexits Communication line used to connect Che...

Page 5: ...box Install door back box 5 8 dia 3 Connect cable wires to same color power transfer door side wires Install door side of EPT 10 shown or finish installing electric hinge 4 Slide module into cover plate as shown 1 Remove end cap end cap bracket and cover plate from Chexit device End cap bracket Cover plate End cap Support hinge end of mechanism case while end cap bracket is not installed CAUTION ...

Page 6: ...odule and slide cover plate half way into mechanism case Make three connections shown Mechanism case 7 Solenoid connectors Position solenoid connectors as shown Pull cable slack behind module while slowly sliding module in Push cable connector away from cover plate while sliding past end of mechanism case 5 Install key cylinder if available otherwise continue with step No 6 Red plastic plate bevel...

Page 7: ...green and white wires 2 If external inhibit not used connect green and white wires together Red LED does not light Power not reaching Chexit Replace reset AC fuse circuit breaker check power supply input output voltages check input voltage at Chexit cable connector Red LED on solid then flashes fast and horn sounds 1 Pushpad pressed 2 Pushpad switch disconnected 1 Release the pushpad 2 Connect pus...

Page 8: ... switch is used the Chexit arms 2 5 seconds after the door closes 6 If you are using a door position switch but you want the full rearm time to expire before the Chexit arms call Von Duprin at 1 888 371 7331 and get instructions from Electrical Technical Support 7 For proper operation the rearm time of each ganged Chexit must differ by at least 2 seconds Location of Chexit option switches OPTIONS ...

Reviews: