52
7.
Specifications
The chapter provides the UPS specifications.
7.1 Conformity And Standards
The UPS has been designed to conform to the European and international standards listed in Table
7-1.
Table 7-1 European and international standards
Item
Normative reference
Uninterruptible power systems (UPS) –Part 1:
General and safety requirements for UPS
IEC/EN62040-1
Electromagnetic compatibility (EMC) requirements
for UPS
IEC/EN62040-2
Method of specifying the performance and test
requirements of UPS
IEC/EN62040-3
Notes:
ESD
IEC/EN 61000-4-2 Level 3
RS
IEC/EN 61000-4-3 Level 3
EFT
IEC/EN 61000-4-4 Level 3
Surge
IEC/EN 61000-4-5 Level 3
CS
IEC/EN 61000-4-6 Level 3
Power-Frequency Magnetic field IEC/EN 61000-4-8 Level 3
Low Frequency Signals
IEC/EN 61000-2-2 Level 10V
Conduction
IEC/EN62040-2 Category C3
Radiation
IEC/EN62040-2 Category C3
7.2 Environmental Characteristics
Table 7-2 Environmental characteristics
Item
Unit
Specifications
Noise within 1 m
dB
Max. 75
Altitude
m
≤1000, derate power by 1% per 100m between
1000m and 2000m
Relative humidity
% RH
0 ~ 95, non condensing
Operating temperature
°C
0 ~ 40°C
(Output capacity will be derated when
temperature is over 30°C. It will be derated to
90% at 35°C and 80% at 40°C.
Storage and transport
temperature for UPS
°C
-15 ~ 60