5.
To avoid theft, you may add a lock
between mounting plate and inverter.
NOTE:
Please follow below requirements to
choose suitable lock.
5.
Grid (AC) Connection
5-1. Preparation
Before connecting to AC utility, please install a
separate
circuit breaker between inverter and
AC utility. This will ensure the inverter can be securely disconnected under load.
NOTE1:
Although this inverter is equipped with a fuse (F1 point on PCB, 250VAC/20A), it’s
still necessary to install a separate circuit breaker for safety consideration. Please use
250VAC/20A circuit breaker.
NOTE2:
If you want to add a manual RCMU, it shall be type B.
WARNING!
It's very important for system safety and efficient operation to use appropriate
cable for grid connection. To reduce risk of injury, please use the proper recommended cable
size as below.
Suggested cable requirement for AC wire
Model
Diameter(mm) Conductor cross-section
(mm
2
)
AWG no. Temperature
EnerSolar
3kW
6± 0.2
≥3
≤12
125°C
5-2. Connecting to the AC Utility
Step 1: Check the grid voltage and frequency with an AC voltmeter. It should be the same to
“VAC” value on the product label.
Step 2: Turn off the circuit breaker.
Step 3: Insert utility cable through cable gland. Connect wires according to polarities
indicated on terminal block.
L
→
LINE (brown or black)
G
→
Ground (yellow-green)
N
→
Neutral (blue)
Step 4: Fasten the gland plate with attached screws.
Step 5: Twist the gland so that the cable is firmly
connected.