Positive terminal connection
Step 2: Remove the cover of PV modules. Check the input voltage of PV modules. The
acceptable input voltage of the solar inverter is 125VDC - 500VDC.
The maximum current load
of each PV input connector is 10A.
Step 3: Disconnect the circuit breaker.
Step 4: Check correct polarity of connection cable from PV modules and PV input connectors.
Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector.
Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
WARNING!
It's very important for system safety and efficient operation to use appropriate
cable for grid connection. To reduce risk of injury, please use the proper recommended cable
size as below.
Suggested cable requirement for AC wire
Model
Diameter(mm) Conductor cross-section
(mm
2
)
AWG no. Temperature
EnerSolar
3kW
6± 0.2
≥3
≤12
125°C
CAUTION:
Exceeding the maximum input voltage can destroy the unit!! Check the system
before wire connection.