L.  Cable Size Selection 

 

Wire Size (AWG)  Area (mm

2

)  Maximum one-way distance 

(feet) for 2% Voltage loss 

(15A) 

Maximum one-way distance 

(feet) for 2% Voltage loss 

(20A) 

Maximum one-way distance 

(feet) for 2% Voltage loss 

(30A) 

10 

5.26 

15.3 

11.5 

6.7 

8.37 

24 

18 

10.3 

13.3 

38 

29 

15 

21.2 

60 

45 

28 

33.6 

96 

72 

45 

1/0 

53.5 

154 

116 

73 

2/0 

67.4 

192 

144 

90 

4/0 

107 

282 

212 

142 

  Table: Selection of cable size and length versus current 

 

M.  Fault Indications 

 

PROTECTIONS & FAULT INDICATIONS WITH CAUSES 

 

PROTECTION / FAULT 

FAULT 

LED 

OTP LED  CHARGER OUTPU: OFF= No Output  REMOTE CONTROL UNIT &  

LCD Fault Display

 

REMARKS 

Output power decreases due to 

high operating ambient   

temperature   

OFF   

Flashing   

ON 

At reduced power in 25% step leading 

to output off high temperature protection 

see next row

 

no specific indication for high 

temperature decreased output   

Auto return to full set 

power gradually as 

unit temp cools down   

charger over heat, OTP 

protection on   

Solid 

ON

  Solid 

ON

 

OFF 

Manual power on off reset after fault 

cleared

 

Alarm flash &    Buzzer on 

Charger 

High Temp”

 

 

Charger preset to reduced output 

power 

OFF   

OFF 

ON At reduced output power as selected   

Indicates 

xx% Power Set”

 

This is not a fault!! 

So no specific 

indication   

Battery over heat detected by 

remote temp sensor at (60

°

C) 

Flashing   

Solid

 ON

 

OFF 

Manual power on off reset after fault 

cleared

 

Alarm flash & Buzzer on 

Bat Over 

Temp

 

 

Fan not working or stuck   

Flashing 

Flashing   

OFF 

Manual power on off reset after fault 

cleared

 

Alarm flash & Buzzer on 

Fan Fault

    

Output Over Voltage Protection 

when output voltage is 4% 

higher than it should be for the 

battery type and charge stage   

Solid 

ON

  OFF 

OFF 

Manual power on off reset after fault 

cleared 

 

Alarm flash & Buzzer on 

Output V 

High

 

To protect battery and 

load connected. 

Overload/ Over Current 

Protection when output current 

is 10% higher than the rated 

maximum level   

Solid

 ON

    OFF   

OFF 

Manual power on off reset after fault 

cleared 

 

Alarm flash & Buzzer on 

Overload”

  To protect charger   

Short Circuit for > 20 sec   

Solid 

ON 

  OFF   

OFF 

Manual power on off reset after fault 

cleared 

 

Alarm flash & Buzzer on 

Output 

Shorted

 

 

Short Circuit for < 20 sec   

OFF 

OFF 

ON

 Charger returns to normal after fault 

cleared   

 

 

Reverse Polarity Protection  

(Thermal Fuse)   

Solid 

ON

  OFF   

OFF

 Manual Power on off reset after 

correct fuse replaced 

 

Alarm flash & Buzzer on                                  

WRONG POLARITY”

 

 

Bulk 4 hour soft start timer 

charging reaches 4 hours 

because battery voltage is 

less than 24V for 4 hours

Solid ON  OFF 

OFF 

Manual Power on off reset. 

Disconnect or switch off active load,   

Check & set output to maximum

 

Alarm flashes & Buzzer on Fault 

mode shows 

“DC Voltage Low” 

EARLY WARNING 

for Battery Capacity, 

load and charger not 

balanced.   

 

 

 

 

 

 

 

 

 

Summary of Contents for BC-2415P

Page 1: ...cause risk of fire electric shock or equipment damage Disconnect the mains supply before connecting or disconnecting the links to the battery If the charger does not work properly or if it has been damaged unplug its AC and DC connection Do not use this charger in connection with any medical device or life support system This appliance is not intended for use by persons including children with red...

Page 2: ...el AGM LiFePO4 Calcium Calcium and now also Lead Crystal batteries There are also two User programmable charging profiles for the professional users via the USB port by personal computer In addition the programmed maintenance charge provides a timely Equalization charge for the Wet lead acid battery Almost all the protections are controlled by the Micro Processor On start up the charger runs a ser...

Page 3: ...minal s 10 Ventilation Fan 11 Inlet AC socket with Mains fuse holder 12 Temperature Sensor Socket Connection to Battery Temperature sensor accessory Sensor to increase decrease charging voltage at low high battery temperature B Using the charger 1 Check the supplied accessories AC cord Remote Battery temperature sensor CD software USB cable are with the package 2 Remove the magnetic dummy remote c...

Page 4: ...he operation of connected powered appliance or connections E Battery Charger Installation and Connection Observe the warnings safety precautions before rushing to install and operate the charger Check battery condition fill up cells for wet battery clean battery poles Secure the battery charger in a well ventilated place make sure the mounting surface is flat and without soft covering material or ...

Page 5: ...orption stage Charging current will now decrease gradually until a pre set value at which the charger then automatically switches to Float Stage The max Absorption time is also controlled by the time in Bulk charge and battery type selected Stage 3 THE UO PHASE FLOAT mode Constant voltage charging Float LED is ON In Float stage the battery is full and only takes in the amount of current necessary ...

Page 6: ...to equalization by charger itself Once Auto is selected the charger will start Equalization automatically if charger stays in Float mode for over 21 days After entering into this mode the Absorption indicator Amber LED will flash the Equalization will run for 240 minutes The charger will then go back to Float once completed Remark 1 This mode only can be operated at WET Flooded selection Battery S...

Page 7: ...mote temp sensor at 60 C Flashing Solid ON OFF Manual power on off reset after fault cleared Alarm flash Buzzer on Bat Over Temp Fan not working or stuck Flashing Flashing OFF Manual power on off reset after fault cleared Alarm flash Buzzer on Fan Fault Output Over Voltage Protection when output voltage is 4 higher than it should be for the battery type and charge stage Solid ON OFF OFF Manual pow...

Page 8: ...oad and charger not balanced Battery does not get full charge All indicator LED work normally and sequentially OTP LED flashing Bad battery connection Battery type select switch in wrong setting Battery capacity too large Ambient temperature too low Battery has damaged cell or battery is too old Wrong set the lower power level Check for loose contact right cable size cable integrity Recheck batter...

Page 9: ...ad 230V 2 5A 3 5A 5 0A Protection Overload 90 110 Rated Output Current or 50 Rated Output Current Soft Charge Protection Type Constant Current Limiting recovers Automatically after Fault Condition is Removed Short Circuit Recovers Automatically if Fault Condition is Removed within 20 seconds Otherwise the charger will shut down until re start the charger again Reverse Polarity Automotive type Blad...

Page 10: ...r level set type of fault with alarm etc and can remote control the output terminal On OFF trigger the Equalization charging for wet battery and force charger to float mode It can be mounted on BC charger by replacing the dummy cover on the front panel or remotely mounted with 10m extension cable going through the unplugged hole at the front of the dummy panel II Connection 1 10 Meters Phone Cable...

Page 11: ...r output ON and OFF Green LED is illuminated when output is ON 2 Alarm Can be silenced or audible by toggling this button default is audible Red LED will illuminate when fault occurred 3 Func To toggle charger setting Menu and select scrolling to make display continue to scroll all setting See optional remote programming section 4 Set To confirm the chosen feature you selected ...

Page 12: ...e Version Displays the current control software version Remote Short cut 1 Press and hold the SET button for 5 seconds and release the button to enter Equalization mode Equalization selection slide switch on main unit should be selected at manual position 2 Press and hold the Func button for 5 seconds and release the button to force the charger to Float mode V Fault Indication 1 Charger High Temp ...

Reviews: