RCD test - Tripping time of RCCB/RCD
Measurement range
Resolution
Accuracy
10 ms - 500 ms
1 ms
±(5% + 2)
Testing of current/polarity: 30 mA sinusoidal/0° and 180°, 150 mA sinusoidal /0° and 180°
Factory Set Pass/Fail Preset limit: 200 ms (30 mA), 40 ms (150 mA)
Leakage Current measurement with 3-phase adapter - Protective conductor current (direct measurement
method with optional measurement adapters)
Measurement range
Resolution
Accuracy
0.25 mA - 9.99 mA
0.01 mA
±(5% + 2)
Test voltage: 3x 400 V ±10%
Rated current: 16 A
Factory Set Pass/Fail Preset limit: 3.5 mA
Voltage measurement - Voltage measurement at external earthed socket
Measurement range
Resolution
Accuracy
5 V - 270 V/AC
1 V
±(5% + 2)
Measured and display: Voltage between L and N, L and PE, N and PE
Note: all Factory Set Pass/Fail limits are preset according to DIN VDE 0701-0702 and ÖVE/ÖNORM E 8701-1