background image

7

Mynute

the provision of a safe and satisfactory flue and
termination. The location must also permit an
adequate air supply for combustion purposes
and an adequate space for servicing and air
circulation around the appliance. Where the
installation of the appliance will be in an unusual
location special procedures may be necessary,
refer to I.S. 813 for detailed guidance on this
aspect.
A compartment used to enclose the appliance
must be designed and constructed specifically
for this purpose. An existing compartment/
cupboard may be utilised provided that it is
modified to suit.
This appliance is not suitable for external
installation.

3A.3

GAS SUPPLY
The gas meter – as supplied by the gas supplier
– must be checked to ensure that it is of adequate
size to deal with the maximum rated input of all
the appliances that it serves. Installation pipes
must be fitted in accordance with I.S. 813.
Pipe work from the meter to the appliance must
be of adequate size. Pipes of a smaller size than
the appliance gas inlet connection must not be
used. The installation must be tested for
soundness in accordance with I.S. 813.
If the gas supply serves more than one appliance,
it must be ensured that an adequate supply is
maintained to each appliance when they are in
use at the same time.

3A.4

FLUE SYSTEM
The terminal should be located where the dispersal
of combustion products is not impeded and with
due regard for the damage and discoloration that
may occur to building products located nearby.
The terminal must not be located in a place where
it is likely to cause a nuisance (see I.S. 813).
In cold and/or humid weather, water vapour may
condense on leaving the terminal; the effect of
such pluming must be considered.
If installed less than 2m above a pavement or
platform to which people have access (including
balconies or flat roofs) the terminal must be
protected by a guard of durable material. The
guard must be fitted centrally over the terminal.
Refer to I.S. 813, when the terminal is 0.5 metres
(or less) below plastic guttering or 1 metre (or
less) below painted eaves.

3A.5

AIR SUPPLY
The following notes are intended for general
guidance only.
This appliance is a room-sealed, fan-flued boiler,
consequently it does not require a permanent air
vent for combustion air supply.
When installed in a cupboard or compartment,
ventilation for cooling purposes is also not
required.

3A.6

WATER CIRCULATION
Specific recommendations are given in I.S. 813.

The following notes are for general guidance
only.

3A.6.1 PIPEWORK

It is recommended that copper tubing be used in
conjunction with soldered capillary joints.
Where possible pipes should have a gradient to
ensure air is carried naturally to air release points
and that water flows naturally to drain cocks.
Except where providing useful heat, pipes should
be insulated to avoid heat loss and in particular to
avoid the possibility of freezing. Particular attention
should be paid to pipes passing through ventilated
areas such as under floors, loft space, and void
areas.

3A.6.2 AUTOMATIC BY-PASS

The appliance has a built-in automatic by-pass,
consequently there is no requirement for an
external by-pass, however the design of the
system should be such that it prevents boiler
‘cycling.

3A.6.3 DRAIN COCKS

These must be located in accessible positions to
facilitate draining of the appliance and all water
pipes connected to the appliance.

3A.6.4 AIR RELEASE POINTS

These must be positioned at the highest points in
the system where air is likely to be trapped. They
should be used to expel trapped air and allow
complete filling of the system.

3A.6.5 EXPANSION VESSEL

The appliance has an integral expansion vessel
to accommodate the increased volume of water
when the system is heated. It can accept up to 10
litres of expansion from within the system,
generally this is sufficient, however if the system
has an unusually high water content, it may be
necessary to provide additional expansion
capacity.

3A.6.6 FILLING POINT

A method for initial filling of the system and
replacing water lost during servicing etc. must be
provided. A typical arrangement is shown in
figure 5.  You should ensure this method of filling
complies with the local water authority regulations.

3A.6.7 LOW PRESSURE SEALED SYSTEM

An alternative method of filling the system would
be from an independent make-up vessel or tank
mounted in a position at least 1 metre above the
highest point in the system and at least 5 metres
above the boiler (fig. 5).
The cold feed from the make-up vessel or tank
must be fitted with an approved non-return valve
and stopcock for isolation purposes. The feed
pipe should be connected to the return pipe as
close to the boiler as possible.

3A.6.8 FREQUENT FILLING

Frequent filling or venting of the system may be
indicative of a leak. Care should be taken during

Summary of Contents for Mynute 28e

Page 1: ...Installation Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER Mynute 28e 35e...

Page 2: ...l lighting 14 5 7 Checking the burner pressure 15 5 8 Final flushing of the heating system 15 5 9 Setting the boiler operating temperature 15 5 10 Setting the system design pressure 15 5 11 Regulating...

Page 3: ...e selector switch The Vokera Mynute is a central heating boiler which by design incorporateselectronicignition circulatingpump expansion vessel safety valve pressure gauge and automatic by pass Itispr...

Page 4: ...rate to 75 for a period of 15 minutes Thereafter the boiler s output will either be increase to maximum or modulate to suit the set requirement When the appliance reaches the desired temperature the...

Page 5: ...m Top 150 mm from casing or 25 mm above flue elbow whichever is applicable Bottom 150 mm Front 600 mm 2 6 Connections Flow return 22 mm compression Gas 15 mm compression Safety valve 15 mm copper 2 7...

Page 6: ...otland Regulation and Building Standards Northern Ireland Regulations It should be in accordance also with any relevant requirementsofthelocalauthorityandtherelevant recommendationsofthefollowingBriti...

Page 7: ...tes are for general guidance only 3 6 1 PIPEWORK ItisrecommendedthatcoppertubingtoBS2871Part 1 is used in conjunction with soldered capillary joints Where possible pipes should have a gradient to ensu...

Page 8: ...ensate discharge into a suitable drain or soil pipe The condensate outlet pipe must be connectedtothedraininaccordancewithbuilding regulations or other rules in force 3 11 INHIBITORS Vokera recommend...

Page 9: ...pboard or compartment ventilation for cooling purposes is also not required 3A 6 WATER CIRCULATION Specific recommendations are given in I S 813 The following notes are for general guidance only 3A 6...

Page 10: ...cted with a 3 amp fuse The method of connection to the mains electricity supply must allow for complete isolation from the supply The preferred method is by using a double pole switch with a contact s...

Page 11: ...0mm dimension X 600mm 920mm dimension X 833mm dimension X 750mm 1500mm N A N A N A 4 4 2 MAXIMUM FLUE LENGTHS 4 5 FITTING THE FLUE The top flue outlet permits both horizontal and vertical flue applica...

Page 12: ...pplied with the terminal kit to the top of the boilerusingtheclips screws gasketssupplied Theadditionalbend extensionshaveaninternal push fit connection care should be taken to ensure that the correct...

Page 13: ...entric flue system It can be used for horizontal or vertical applications however the twin flue system must be converted to the dedicated concentric flue kit for termination It is essential that the i...

Page 14: ...e wall The air inlet pipe must always be level with or below that of the exhaust pipe Depending on site conditions it may be preferable to install the terminal assembly prior to fitting the twin flue...

Page 15: ...arge pipe to the safety valve outlet and tighten The discharge pipe must have a continuous fall away from the appliance to outside and allow any water to drain awaytherebyeliminatingthepossibilityoffr...

Page 16: ...er and heating system as described in 5 3 5 5 PRE OPERATION CHECKS Before attempting to initial lighting of the appli ance the following checks must be carried out ensure all gas service valves from t...

Page 17: ...s 45 psig To lower the system pressure to the required value pull lever on head of safety valve to release water until the required figure registers on the pressure gauge see fig 1 5 11 REGULATING THE...

Page 18: ...to the commissioning section and or re placement of parts section for detailed instruction if required 6 3 REPLACEMENT OF COMPONENTS Although it is anticipated that this appliance will give years of r...

Page 19: ...minal cover then remove cover after carefully taking note of all wiring connections disconnect all wiring from the PCB locate and remove the PCB securing screws remove PCB Replace in the reverse order...

Page 20: ...dure as de scribed in 6 4 Unclip and remove the air chamber cover gently pull the cover towards you before lifting and disengaging Locate and remove the six screws that secure the front combustion cov...

Page 21: ...air chamber Discon nect the electrode lead and burner thermostat wires Disconnect the outlet gas pipe and the flow return pipes from the air chamber Locate and remove the 2 screws that secure the low...

Page 22: ...al supply and attach a suitable manometer to the gas valve outlet test nipple Remove the compensator tube 28e only 7 3 1 SETTING THE MAXIMUM BURNER PRESSURE Light the boiler as described in 5 6 and co...

Page 23: ...rry out the following voltage tests connect test leads between the Live Neutral connectionsattheapplianceterminalstrip see fig 16 the meter should read approximately 230V ac If so proceed to next stag...

Page 24: ...boiler does not reset refer to the following section and the detailed fault finding flowcharts overleaf FAULT CODE 01 Fault code 01 appears when the burner has failed to ignite or the flame supervisi...

Page 25: ...b YES Is there 5vdc across terminals M9 1 M9 2 on main PCB YES Is there 5vdc across terminals M2 1 M2 2 on main PCB Go to test B YES Replace display PCB YES NO Replace main PCB NO Replace ribbon cable...

Page 26: ...connections YES NO Is there 230V between terminals M12 1 M12 2 YES Is there 230V between L N terminals of fan Check wiring continuity YES Replace fan Is there 24Vdc between M5 3 M3 3 NO NO Replace mai...

Page 27: ...DC between terminals M3 10 M3 11 on PCB NO Checking wiring connections or analog air sensor NO YES Replace main PCB YES Check wiring connections check water pressure switch NO YES Checking wiring conn...

Page 28: ...ok NO NO YES Replace gas valve Check gas Is ionisation voltage ok NO YES Replace ignition PCB NO Replace spark electrode Replace spark electrode FAULT FINDING TEST E Mynute 28e 35e turn the selector t...

Page 29: ...8 3 INSTALLATION OF VOKERA TIME CLOCK 24 hours 7 day versions Isolate the appliance from the electrical supply and remove the casing as described in 4 7 1 Remove the circular blanking disc from the cl...

Page 30: ...28 Mynute S plan system external programmer or integral Vokera programmer Fig 28...

Page 31: ...rmostat Add if programmer has heating only position Twin channel programmer 230V supply 50Hz Wiring centre Room thermostat White Grey Orange Blue Green Yellow Vokera twin channel programmer Appliance...

Page 32: ...PE Gas valve solenoids B C B Burner control board B E B Boiler control board D B Secondary board JP8 Natural gas or L P G selector Fig 30 JP9 Timer on off selector PT2 Central heating temperature cont...

Page 33: ...Gas valve solenoids B C B Burner control board B E B Boiler control board S B Secondary board JP8 Natural gas or L P G selector JP9 Timer on off selector PT2 Central heating temperature control PT1 S...

Page 34: ...32 Mynute NOTE L N E CONNECTION IS ADVISABLE CONTROL SWITCHING OF TIME CLOCK AND ROOM THERMOSTAT IS 230 V a c FUNCTIONAL DIAGRAM 28e Fig 32...

Page 35: ...33 Mynute FUNCTIONAL DIAGRAM 35e NOTE L N E CONNECTION IS ADVISABLE CONTROL SWITCHING OF TIME CLOCK AND ROOM THERMOSTAT IS 230 V a c Fig 33...

Page 36: ...0024731 26 Instrumental panel R10023051 R10024756 31 Case R1922 R2062 38 Control printed circuit board R10020477 R10020477 39 Spring R1862 R1862 40 Door panel R10022860 R10024757 43 Push push cover R1...

Page 37: ...044 7 Heating by pass valve R1552 R1552 9 Heating distributor manifold R10021821 R10021821 22 Safety valve R1806 R1806 23 Pipe R10023065 R10023065 27 Heating cock R1789 R1789 31 Venting plugs kit R010...

Page 38: ...ing harness R1845 R1845 6 Pump pipe R1917 R10023209 7 Pipe R1847 R2051 8 Heat exchanger R2378 R10024580 9 Pipe R10021041 R10020519 10 Pipe R10022859 R10024754 11 Bracket R1642 R1642 15 Automatic air v...

Page 39: ...fle R2069 9 Burner plate R5172 11 Air box clip R0442 R0442 12 Gas pipe R1839 R1839 13 Gas valve R10021021 R10021021 14 Gas pipe R1840 R1840 15 Gas cock R1787 R1787 16 Cover assembly R10020217 R1002043...

Page 40: ...sembly R5907 R1968 10 Fan R6492 R10024577 12 Fan to flue connector R10023183 R10023183 16 Clamp for 60 diam tube R5916 R5916 17 Washer clamp R5917 R5917 19 Fan flue connection R8083 R8083 20 Block wit...

Page 41: ...of the boiler burner pressure is not compromised due to a high flow temperature For details of converting boilers to LPG please refer to the instructions supplied with the relevant conversion kit 10...

Page 42: ...40 Mynute...

Page 43: ...41 Mynute...

Page 44: ...eneral Enquiries Tel 0870 333 0520 Fax 01442 281403 After Sales Service Tel 0870 333 0220 Vok ra Ireland West Court Callan Co Kilkenny Tel 05677 55057 Fax 05677 55060 Vok ra Ltd reserve the right to c...

Reviews: