background image

14

Mynute

5.1

GAS SUPPLY INSTALLATION
Inspect the entire installation including the gas
meter, test for soundness and purge. Refer to BS
6891 for specific instruction.

5.2

THE HEATING SYSTEM
The appliance contains components that may
become damaged or rendered inoperable by oils
and/or debris that are residual from the installa-
tion of the system, consequently it is essential
that the system be flushed in accordance with the
following instructions.

5.3

INITIAL FILLING OF THE SYSTEM
Ensure both flow & return service valves are
open, remove appliance casing as described in
4.7.1, identify the automatic air release valve and
loosen the dust cap by turning cap anti-clockwise
one full turn. IMPORTANT, THERE ARE NO
MANUAL AIR RELEASE VALVES LOCATED
ON THE APPLIANCE. Ensure all manual air
release valves located on the heating system are
closed. Using the method of filling as described in
fig. 5, slowly proceed to fill the system. As water
enters the system the pressure gauge will begin
to rise. Once the gauge has reached 1bar close
the filling valve and begin venting all manual air
release valves, starting at the lowest first. It may
be necessary to go back and top-up the pressure
until the entire system has been filled. Inspect the
system for water soundness, rectifying any leaks.

SECTION 5      COMMISSIONING

5.4

INITIAL FLUSHING
The whole of the heating system must be flushed as
detailed in 5.8. Open all radiator or heating valves and
the appliance flow & return service valves. Drain the
boiler and system from the lowest points. Open the
drain valve full bore to remove any installation
debris from the boiler prior to lighting. Refill the
boiler and heating system as described in 5.3.

5.5

PRE-OPERATION CHECKS
Before attempting to initial lighting of the appli-
ance, the following checks must be carried out:

ensure all gas service valves from the meter to
the appliance are open and the supply pipe has
been properly purged;

ensure the proper electrical checks have been
carried out (see 7.7), particularly continuity,
polarity and resistance to earth;

ensure the 3 amp fuse – supplied with the
appliance – has been fitted;

ensure the system has been filled, vented, and
the pressure set to 1 bar;

ensure the flue system has been fitted properly
and in accordance with the instructions;

ensure all appliance service valves are open.

5.6

INITIAL LIGHTING
Ensure the electrical supply to the appliance is
switched on. Switch the time clock or programmer
to an ‘on’ position and ensure all external controls

Fig.15

4.7.3

CONNECTING THE MAINS (230V) INPUT (see
fig. 16)
Remove the terminal block cover as described in
4.7.2. Pass the cable through the cable anchorage
(see fig. 6). On the terminal block there are 7
terminals from Right to Left, they are:
1 LIVE
2 NEUTRAL
3 230V output
4 230V input
5 (spare)
6 (spare)
7 (spare)
8 (spare)

Connect the supply cable wires (live & neutral)
to their corresponding terminals on the
appliance terminal block. Connect the EARTH
wire to the EARTH block (see fig. 16) ensuring
that it’s left slightly longer that the others, this
will prevent strain on the earth wire should the
cable become taut.
Do not remove the link wire (between 3 & 4)
unless additional external controls are to be fitted
(see section 8). Re-fit the appliance terminal
block cover.
The securing screw on the cable anchorage
should now be tightened. This must be done
before the control fascia is re-fitted in the upright
position. The appliance casing and screws can
now be re-fitted.

Fig. 16

Appliance

terminal strip

Summary of Contents for Mynute 28e

Page 1: ...Installation Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER Mynute 28e 35e...

Page 2: ...l lighting 14 5 7 Checking the burner pressure 15 5 8 Final flushing of the heating system 15 5 9 Setting the boiler operating temperature 15 5 10 Setting the system design pressure 15 5 11 Regulating...

Page 3: ...e selector switch The Vokera Mynute is a central heating boiler which by design incorporateselectronicignition circulatingpump expansion vessel safety valve pressure gauge and automatic by pass Itispr...

Page 4: ...rate to 75 for a period of 15 minutes Thereafter the boiler s output will either be increase to maximum or modulate to suit the set requirement When the appliance reaches the desired temperature the...

Page 5: ...m Top 150 mm from casing or 25 mm above flue elbow whichever is applicable Bottom 150 mm Front 600 mm 2 6 Connections Flow return 22 mm compression Gas 15 mm compression Safety valve 15 mm copper 2 7...

Page 6: ...otland Regulation and Building Standards Northern Ireland Regulations It should be in accordance also with any relevant requirementsofthelocalauthorityandtherelevant recommendationsofthefollowingBriti...

Page 7: ...tes are for general guidance only 3 6 1 PIPEWORK ItisrecommendedthatcoppertubingtoBS2871Part 1 is used in conjunction with soldered capillary joints Where possible pipes should have a gradient to ensu...

Page 8: ...ensate discharge into a suitable drain or soil pipe The condensate outlet pipe must be connectedtothedraininaccordancewithbuilding regulations or other rules in force 3 11 INHIBITORS Vokera recommend...

Page 9: ...pboard or compartment ventilation for cooling purposes is also not required 3A 6 WATER CIRCULATION Specific recommendations are given in I S 813 The following notes are for general guidance only 3A 6...

Page 10: ...cted with a 3 amp fuse The method of connection to the mains electricity supply must allow for complete isolation from the supply The preferred method is by using a double pole switch with a contact s...

Page 11: ...0mm dimension X 600mm 920mm dimension X 833mm dimension X 750mm 1500mm N A N A N A 4 4 2 MAXIMUM FLUE LENGTHS 4 5 FITTING THE FLUE The top flue outlet permits both horizontal and vertical flue applica...

Page 12: ...pplied with the terminal kit to the top of the boilerusingtheclips screws gasketssupplied Theadditionalbend extensionshaveaninternal push fit connection care should be taken to ensure that the correct...

Page 13: ...entric flue system It can be used for horizontal or vertical applications however the twin flue system must be converted to the dedicated concentric flue kit for termination It is essential that the i...

Page 14: ...e wall The air inlet pipe must always be level with or below that of the exhaust pipe Depending on site conditions it may be preferable to install the terminal assembly prior to fitting the twin flue...

Page 15: ...arge pipe to the safety valve outlet and tighten The discharge pipe must have a continuous fall away from the appliance to outside and allow any water to drain awaytherebyeliminatingthepossibilityoffr...

Page 16: ...er and heating system as described in 5 3 5 5 PRE OPERATION CHECKS Before attempting to initial lighting of the appli ance the following checks must be carried out ensure all gas service valves from t...

Page 17: ...s 45 psig To lower the system pressure to the required value pull lever on head of safety valve to release water until the required figure registers on the pressure gauge see fig 1 5 11 REGULATING THE...

Page 18: ...to the commissioning section and or re placement of parts section for detailed instruction if required 6 3 REPLACEMENT OF COMPONENTS Although it is anticipated that this appliance will give years of r...

Page 19: ...minal cover then remove cover after carefully taking note of all wiring connections disconnect all wiring from the PCB locate and remove the PCB securing screws remove PCB Replace in the reverse order...

Page 20: ...dure as de scribed in 6 4 Unclip and remove the air chamber cover gently pull the cover towards you before lifting and disengaging Locate and remove the six screws that secure the front combustion cov...

Page 21: ...air chamber Discon nect the electrode lead and burner thermostat wires Disconnect the outlet gas pipe and the flow return pipes from the air chamber Locate and remove the 2 screws that secure the low...

Page 22: ...al supply and attach a suitable manometer to the gas valve outlet test nipple Remove the compensator tube 28e only 7 3 1 SETTING THE MAXIMUM BURNER PRESSURE Light the boiler as described in 5 6 and co...

Page 23: ...rry out the following voltage tests connect test leads between the Live Neutral connectionsattheapplianceterminalstrip see fig 16 the meter should read approximately 230V ac If so proceed to next stag...

Page 24: ...boiler does not reset refer to the following section and the detailed fault finding flowcharts overleaf FAULT CODE 01 Fault code 01 appears when the burner has failed to ignite or the flame supervisi...

Page 25: ...b YES Is there 5vdc across terminals M9 1 M9 2 on main PCB YES Is there 5vdc across terminals M2 1 M2 2 on main PCB Go to test B YES Replace display PCB YES NO Replace main PCB NO Replace ribbon cable...

Page 26: ...connections YES NO Is there 230V between terminals M12 1 M12 2 YES Is there 230V between L N terminals of fan Check wiring continuity YES Replace fan Is there 24Vdc between M5 3 M3 3 NO NO Replace mai...

Page 27: ...DC between terminals M3 10 M3 11 on PCB NO Checking wiring connections or analog air sensor NO YES Replace main PCB YES Check wiring connections check water pressure switch NO YES Checking wiring conn...

Page 28: ...ok NO NO YES Replace gas valve Check gas Is ionisation voltage ok NO YES Replace ignition PCB NO Replace spark electrode Replace spark electrode FAULT FINDING TEST E Mynute 28e 35e turn the selector t...

Page 29: ...8 3 INSTALLATION OF VOKERA TIME CLOCK 24 hours 7 day versions Isolate the appliance from the electrical supply and remove the casing as described in 4 7 1 Remove the circular blanking disc from the cl...

Page 30: ...28 Mynute S plan system external programmer or integral Vokera programmer Fig 28...

Page 31: ...rmostat Add if programmer has heating only position Twin channel programmer 230V supply 50Hz Wiring centre Room thermostat White Grey Orange Blue Green Yellow Vokera twin channel programmer Appliance...

Page 32: ...PE Gas valve solenoids B C B Burner control board B E B Boiler control board D B Secondary board JP8 Natural gas or L P G selector Fig 30 JP9 Timer on off selector PT2 Central heating temperature cont...

Page 33: ...Gas valve solenoids B C B Burner control board B E B Boiler control board S B Secondary board JP8 Natural gas or L P G selector JP9 Timer on off selector PT2 Central heating temperature control PT1 S...

Page 34: ...32 Mynute NOTE L N E CONNECTION IS ADVISABLE CONTROL SWITCHING OF TIME CLOCK AND ROOM THERMOSTAT IS 230 V a c FUNCTIONAL DIAGRAM 28e Fig 32...

Page 35: ...33 Mynute FUNCTIONAL DIAGRAM 35e NOTE L N E CONNECTION IS ADVISABLE CONTROL SWITCHING OF TIME CLOCK AND ROOM THERMOSTAT IS 230 V a c Fig 33...

Page 36: ...0024731 26 Instrumental panel R10023051 R10024756 31 Case R1922 R2062 38 Control printed circuit board R10020477 R10020477 39 Spring R1862 R1862 40 Door panel R10022860 R10024757 43 Push push cover R1...

Page 37: ...044 7 Heating by pass valve R1552 R1552 9 Heating distributor manifold R10021821 R10021821 22 Safety valve R1806 R1806 23 Pipe R10023065 R10023065 27 Heating cock R1789 R1789 31 Venting plugs kit R010...

Page 38: ...ing harness R1845 R1845 6 Pump pipe R1917 R10023209 7 Pipe R1847 R2051 8 Heat exchanger R2378 R10024580 9 Pipe R10021041 R10020519 10 Pipe R10022859 R10024754 11 Bracket R1642 R1642 15 Automatic air v...

Page 39: ...fle R2069 9 Burner plate R5172 11 Air box clip R0442 R0442 12 Gas pipe R1839 R1839 13 Gas valve R10021021 R10021021 14 Gas pipe R1840 R1840 15 Gas cock R1787 R1787 16 Cover assembly R10020217 R1002043...

Page 40: ...sembly R5907 R1968 10 Fan R6492 R10024577 12 Fan to flue connector R10023183 R10023183 16 Clamp for 60 diam tube R5916 R5916 17 Washer clamp R5917 R5917 19 Fan flue connection R8083 R8083 20 Block wit...

Page 41: ...of the boiler burner pressure is not compromised due to a high flow temperature For details of converting boilers to LPG please refer to the instructions supplied with the relevant conversion kit 10...

Page 42: ...40 Mynute...

Page 43: ...41 Mynute...

Page 44: ...eneral Enquiries Tel 0870 333 0520 Fax 01442 281403 After Sales Service Tel 0870 333 0220 Vok ra Ireland West Court Callan Co Kilkenny Tel 05677 55057 Fax 05677 55060 Vok ra Ltd reserve the right to c...

Reviews: