![VOKERA Maxin 24e Installation & Servicing Instructions Manual Download Page 17](http://html1.mh-extra.com/html/vokera/maxin-24e/maxin-24e_installation-and-servicing-instructions-manual_1044988017.webp)
16
MAXIN 24e & 28e
5.7.4
Pass the cable through one of the cord
anchorage points and connect the wires
Brown to L, Blue to N, and Green/Yellow to
, arrange the cable so that should the
cable slip the anchorage the current carry-
ing conductors become taut before the
earthing conductor.
5.7.5
Securely tighten all terminal screws and
arrange the cable with slack between the
cable anchor and the terminal block.
Tighten the cord anchorage screw until the
cable is secure.
5.7.6
Neatly arrange the external cable in such a
way that unrestricted opening of the controls
fascia is possible without strain on the cable.
5.7.7
External controls may be wired from termi-
nals 1 to 2 on the left hand terminal block
mounted on the back of the front fascia panel
after removing the factory fitted links (see fig.
19A). If a neutral is needed use the terminal
marked N on the terminal strip.
Internal controls (ie. Vokèra time clock) may
be wired from the right hand terminal block
mounted on the back of the front facia after
removing the factory fitted link between 4 &
5. See section 10.
If required pass the external controls cable
through the spare cord anchorage and
arrange the cable so that should the cable
slip the anchorage, the current carrying
conductors become taut before the earthing
conductor.
Fig. 19A
Control panel securing screws
Mains Input &
External Controls
Terminal Block
Internal Controls
Terminal Block