background image

4

This appliance must be installed by a competent
person in accordance with the Gas Safety (Instal-
lation & Use) Regulations.

3.1

RELATED DOCUMENTS
The installation of this water heater must be in
accordance with the relevant requirements of the
Gas Safety (Installation & Use) Regulations, the
Water supply (water fittings) Regulations, the
Water Byelaws Scotland, the Building Standards
(Scotland) Regulation and Building Standards
(Northern Ireland) Regulations.
It should be in accordance also with any relevant
requirements of the local authority and the relevant
recommendations of the following British Standard
Codes of Practice.

3.2

LOCATION OF APPLIANCE
The appliance may be installed in any room or
internal space, although particular attention is
drawn to the requirements of the current I.E.E.
wiring regulations, and in Scotland, the electrical
provisions of the Building Regulations, with
respect to the installation of the appliance in a
room or internal space containing a bath or shower.

When an appliance is installed in a room or
internal space containing a bath or shower, the
appliance or any control pertaining to it must not
be within reach of a person using the bath or
shower.
The location chosen for the appliance must permit
the provision of a safe and satisfactory flue and
termination. The location must also permit an
adequate air supply for combustion purposes
and an adequate space for servicing and air
circulation around the appliance. Where the
installation of the appliance will be in an unusual
location special procedures may be necessary,
BS 6798 gives detailed guidance on this aspect.
A compartment used to enclose the appliance
must be designed and constructed specifically
for this purpose. An existing compartment/cup-
board may be utilised provided that it is modified
to suit.
Details of essential features of compartment/
cupboard design, including airing cupboard in-
stallations, are given in BS 6798. This appliance
is not suitable for external installation.

3.3

GAS SUPPLY
The gas meter – as supplied by the gas supplier
– must be checked to ensure that it is of adequate
size to deal with the maximum rated input of all
the appliances that it serves. Installation pipes

must be fitted in accordance with BS 6891.
Pipe-work from the meter to the appliance must
be of adequate size. Pipes of a smaller size than
the appliance gas inlet connection must not be
used. The installation must be tested for sound-
ness in accordance with BS 6891.
If the gas supply serves more than one appliance,
it must be ensured that an adequate supply is
maintained to each appliance when they are in
use at the same time.

3.4

FLUE SYSTEM
The terminal should be located where the disper-
sal of combustion products is not impeded and
with due regard for the damage and discoloration
that may occur to building products located nearby.
The terminal must not be located in a place where
it is likely to cause a nuisance (see fig. 3).
In cold and/or humid weather, water vapour may
condense on leaving the terminal; the effect of
such pluming must be considered.
If installed less than 2m above a pavement or
platform to which people have access (including
balconies or flat roofs) the terminal must be
protected by a guard of durable material. The
guard must be fitted centrally over the terminal.
Refer to BS 5440 Part 1, when the terminal is 0,5
metres (or less) below plastic guttering  or 1 metre
(or less) below painted eaves.

3.5

AIR SUPPLY
The following notes are intended for general
guidance only.
This appliance is a room sealed, fan-flued water
heater, consequently it does not require a
permanent air vent for combustion air supply.
When installed in a cupboard or compartment,
ventilation for cooling purposes is also not required.

3.6

WATER PIPE WORK
Detailed recommendations are given in BS 5449
Part 1 and BS 6798. The following notes are for
general guidance only.

3.6.1

PIPEWORK
It is recommended that copper tubing to BS 2871
Part 1 is used in conjunction with soldered capil-
lary joints.
Where possible pipes should have a gradient to
ensure air is carried naturally to an outlet and that
water flows naturally to drain cocks.

SECTION 3

GENERAL REQUIREMENTS

BS 5440

PART 1

FLUES

BS 5440

PART 2

FLUES AND VENTILATION

BS 5546

INSTALLATION OF HOT WATER SUPPLIES FOR DOMESTIC PURPOSES

BS 6891

LOW PRESSURE INSTALLATION PIPES

BS 6700

DESIGN, INSTALLATION, TESTING AND MAINTAINENCE OF SERVICES SUPPLYING
WATER FOR DOMESTIC USE

Summary of Contents for AquaNova

Page 1: ...ions THESE INSTRUCTIONS TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems i...

Page 2: ...ner pressure 11 5 6 Setting the outlet temperature 11 5 7 Final checks 11 5 8 Instructing the user 11 Servicing Page 6 1 General 12 6 2 Routine annual servicing 12 6 3 Replacement of components 12 6 4...

Page 3: ...which by design incorporates electronic ignition NTC temperature control continuous gas modulation and status fault indicators Itisproducedasaroomsealed categoryII2H3 appliance suitable for wall moun...

Page 4: ...uitthesetrequirement When the appliance reaches the desired temperature the burner will modulate to maintain thedesiredtemperature Shouldthetemperature continue to increase the burner will shut off wh...

Page 5: ...tric 2 4 metres Minimum horizontal flue length concentric 0 4 metres Maximum vertical flue length concentric 3 6 metres Minimum vertical flue length concentric 1 0 metres Maximum twin flue length hori...

Page 6: ...ith the maximum rated input of all the appliances that it serves Installation pipes must be fitted in accordance with BS 6891 Pipe work from the meter to the appliance must be of adequate size Pipes o...

Page 7: ...bracket template an accessories pack containing the appliance service valves and washers the instruction pack containing the installation servicing instructions user instructions and a 3 amp fuse 4 3...

Page 8: ...m extension 45 bend pair 90 bend Wall bracket 5 380mm 600mm dimension X 600mm 920mm dimension X 833mm dimension X 750mm 1500mm N A N A N A IMPORTANT The flue restrictor ring must be inserted into the...

Page 9: ...exceeds 1 0m NOTE When cutting the horizontal flue terminal or an extensiontotherequiredlength youmustensure that the excess is cut from the plain end of the terminal or extension and that the inner...

Page 10: ...m enables greater flue distances to be achieved see 4 4 2 than that of the standard concentric flue system It can be used for horizontal or vertical applications however the twin flue system must be c...

Page 11: ...twin flue pipes to allow connection to the concentric to twin converter NOTE Before cutting twin flue pipes ensure allowances have been made for connection onto the previous piece and onto the concent...

Page 12: ...ATER OUTLET see fig 4 The appliance is supplied with 15mm connector for the hot water outlet connection connect a 15mm pipe to the outlet of the connector and tighten the nut 4 7 ELECTRICAL CONNECTION...

Page 13: ...meter to the gas valve outlet test nipple see fig 15 Light the appliance as described in 5 4 and compare the reading on the manometer with the values described in 2 2 If adjustement is required follow...

Page 14: ...s such as operating conditions and usage Should the appliance develop a fault the fault finding sectionwillassistindeterminingwhichcomponent is malfunctioning 6 4 COMPONENT REMOVAL PROCEDURE To remove...

Page 15: ...6 9 BURNER INJECTORS AND SPARK SENSE ELECTRODE see fig 18a b c Carry out component removal procedure as de scribed in 6 4 Remove the appliance casing as described in 4 7 1 Locate and remove the ten sc...

Page 16: ...cessary to check it during servicing or if the gas valve has been removed Isolate the appliance from the electrical supply and attach a suitable manometer to the gas valve outlet test nipple Remove th...

Page 17: ...5 3 POLARITY CHECK With the appliance connected to the electrical supply and using a suitable multi meter carry out the following voltage tests connect test leads between the Live Neutral connectionsa...

Page 18: ...very 0 5 seconds Red LED Action required Status Off Off On Flashing on off every 0 5 seconds Off Flashing on off every 0 5 seconds Switched off or at stand by DHW request Flame lockout Overheating Air...

Page 19: ...ECK WIRING AND CONNECTIONS OR SAFETY THERMOSTAT MAINS PRESENT BETWEEN TERMINALS X1 1 X1 2 ON DRIVER BOARD NO REPLACE DRIVER BOARD FUSES OK CHECK FUSES F1 F2 ON DRIVER BOARD RESTART THE TEST REPLACE FU...

Page 20: ...ELECTRODE AND LEAD IS THERE MECHANICAL OPENING OF GAS VALVE SOLENOIDS NO REPLACE A C F BOARD NO DO THE AIR FLOW SWTCH TURN ON CHECK WIRING AND CONNECTIONS AND AIR FLOW SWITCH YES NO ARE THE VENTURI TU...

Page 21: ...2 Vdc IS VOLTAGE ACROSS TERMINALS OF MODULATOR COIL 1 2 Vdc IS WATER TEMPERATURE 60 C WAIT WATER TEMPERATURE 60 C SWITCH WATER THERMOSTAT AT MIN DO BURNER AND FAN SWITCH OFF IS WATER TEMPERATURE 40 C...

Page 22: ...WIRE ON AIR FLOW SWITCH AND PIN 11 ON ACF CHECK OR REPLACE WIRING AND CONNECTIONS A1 YES MAINS PRESENT BETWEEN RED WIRE ON AIR FLOW SWITCH AND PIN 11 ON ACF CHECK OR REPLACE WIRING AND CONNECTIONS IS...

Page 23: ...or further advice on the electrical connection please contact Vokera technical on 0870 333 0520 TR1 DHW temperature control TR2 Selector ON OFF JP1 Natural gas or LPG selector jumper P F Air pressure...

Page 24: ...22 FUNCTIONAL DIAGRAM NOTE L N connection is advisable brown blue purple purple red red grey grey black black white white blue brown pink...

Page 25: ...Lower panel 10020663 16 Cable entry socket 5371 17 Rivet 5037 18 PCB cover 10021120 19 Control panel 10021127 20 Led lens 10020676 21 Selector thermostat knob 10020674 22 Adhesive logo 1471 23 Air cha...

Page 26: ...20668 23 Flow restrictor 9430 24 Inlet pipe 10020666 25 DHW flow switch 10020330 26 Gas valve 10021021 27 Gas valve outlet pipe 10020667 28 Outlet pipe 10020664 29 High limit thermostat 10021235 30 1...

Page 27: ...uring the above procedure This will ensure that the output of the appliance burner pressure is not compromised due to a high outlet temperature For details of converting an appliance to LPG please ref...

Page 28: ...quiries vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reser...

Reviews: