4
This appliance must be installed by a competent
person in accordance with the Gas Safety (Instal-
lation & Use) Regulations.
3.1
RELATED DOCUMENTS
The installation of this water heater must be in
accordance with the relevant requirements of the
Gas Safety (Installation & Use) Regulations, the
Water supply (water fittings) Regulations, the
Water Byelaws Scotland, the Building Standards
(Scotland) Regulation and Building Standards
(Northern Ireland) Regulations.
It should be in accordance also with any relevant
requirements of the local authority and the relevant
recommendations of the following British Standard
Codes of Practice.
3.2
LOCATION OF APPLIANCE
The appliance may be installed in any room or
internal space, although particular attention is
drawn to the requirements of the current I.E.E.
wiring regulations, and in Scotland, the electrical
provisions of the Building Regulations, with
respect to the installation of the appliance in a
room or internal space containing a bath or shower.
When an appliance is installed in a room or
internal space containing a bath or shower, the
appliance or any control pertaining to it must not
be within reach of a person using the bath or
shower.
The location chosen for the appliance must permit
the provision of a safe and satisfactory flue and
termination. The location must also permit an
adequate air supply for combustion purposes
and an adequate space for servicing and air
circulation around the appliance. Where the
installation of the appliance will be in an unusual
location special procedures may be necessary,
BS 6798 gives detailed guidance on this aspect.
A compartment used to enclose the appliance
must be designed and constructed specifically
for this purpose. An existing compartment/cup-
board may be utilised provided that it is modified
to suit.
Details of essential features of compartment/
cupboard design, including airing cupboard in-
stallations, are given in BS 6798. This appliance
is not suitable for external installation.
3.3
GAS SUPPLY
The gas meter – as supplied by the gas supplier
– must be checked to ensure that it is of adequate
size to deal with the maximum rated input of all
the appliances that it serves. Installation pipes
must be fitted in accordance with BS 6891.
Pipe-work from the meter to the appliance must
be of adequate size. Pipes of a smaller size than
the appliance gas inlet connection must not be
used. The installation must be tested for sound-
ness in accordance with BS 6891.
If the gas supply serves more than one appliance,
it must be ensured that an adequate supply is
maintained to each appliance when they are in
use at the same time.
3.4
FLUE SYSTEM
The terminal should be located where the disper-
sal of combustion products is not impeded and
with due regard for the damage and discoloration
that may occur to building products located nearby.
The terminal must not be located in a place where
it is likely to cause a nuisance (see fig. 3).
In cold and/or humid weather, water vapour may
condense on leaving the terminal; the effect of
such pluming must be considered.
If installed less than 2m above a pavement or
platform to which people have access (including
balconies or flat roofs) the terminal must be
protected by a guard of durable material. The
guard must be fitted centrally over the terminal.
Refer to BS 5440 Part 1, when the terminal is 0,5
metres (or less) below plastic guttering or 1 metre
(or less) below painted eaves.
3.5
AIR SUPPLY
The following notes are intended for general
guidance only.
This appliance is a room sealed, fan-flued water
heater, consequently it does not require a
permanent air vent for combustion air supply.
When installed in a cupboard or compartment,
ventilation for cooling purposes is also not required.
3.6
WATER PIPE WORK
Detailed recommendations are given in BS 5449
Part 1 and BS 6798. The following notes are for
general guidance only.
3.6.1
PIPEWORK
It is recommended that copper tubing to BS 2871
Part 1 is used in conjunction with soldered capil-
lary joints.
Where possible pipes should have a gradient to
ensure air is carried naturally to an outlet and that
water flows naturally to drain cocks.
SECTION 3
GENERAL REQUIREMENTS
BS 5440
PART 1
FLUES
BS 5440
PART 2
FLUES AND VENTILATION
BS 5546
INSTALLATION OF HOT WATER SUPPLIES FOR DOMESTIC PURPOSES
BS 6891
LOW PRESSURE INSTALLATION PIPES
BS 6700
DESIGN, INSTALLATION, TESTING AND MAINTAINENCE OF SERVICES SUPPLYING
WATER FOR DOMESTIC USE