TEST RUNNING
Operate according to "key points for test running" on the electric control box cover.
PRECAUTIONS ON REFRIGERANT LEAKAGE
When the refrigerant charge in appliance is more than 1.842kg, following requirments
should be complied with.
Requirments for charge limits in unventilated areas:
The maximum refrigerant charge in appliance shall be in accordance with the following:
m
max
= 2.5 x (LFL)
5/4
x 1.8 x (A)
1/2
or the required minium floor area Amin to install an appliance with refrigerant charge
mc shall be in accordance with following:
A
min
= ( m
c
/ ( 2.5 x (LFL)
5/4
x 1.8))
2
where
m
max
is the allowable maximumm charge in a room, in kg
A
is the room area, in m
2
A
min
is the required minimum room area ,in m
2
m
c
is the refrigerant charge in appliance, in kg
LFL
is the lower flammable limit in kg/m
3
,the value is 0.306 for R32
refrigerant
●
Install mechanical ventilator to reduce the refrigerant thickness, under critical
level. (ventilate regularly).
●
Install leak alarm facility related to mechanical ventilator if you can not regularly
ventilate.
CAUTION
Test running can not start until the outdoor unit has been connected to the power
for 12 hours.
Test running can not start until all the valves are affirmed open.
Summary of Contents for HPS-22CH65AERI/O1 R32
Page 2: ......
Page 53: ...VIVAX HR 50 DODATAK B Dijagram ožičenja s električnim upravljanjem 4 10kW ...
Page 57: ...VIVAX HR ...
Page 58: ... HR VIVAX 1 ...
Page 89: ...VIVAX HR 32 STRUKTURA IZBORNIKA PREGLED ...
Page 90: ... HR VIVAX 33 ...
Page 145: ...VIVAX ENG 50 ANNEX B Electrically controlled wiring diagram 4 10kW ...
Page 149: ...VIVAX ENG ...
Page 150: ... ENG VIVAX 1 ...
Page 181: ...VIVAX ENG 32 MENU STRUCTURE OVERVIEW ...
Page 182: ... ENG VIVAX 33 ...
Page 187: ......
Page 205: ...3 4 3 4 3 4 ...
Page 208: ...ZZZ 9 9 FRP ...