ENG
VIVAX
25
System
Outdoor Unit
Power Current
Compressor
Compressor
Voltage
(V)
Hz
Min.
(V)
Max.
(V)
MCA (A)
TOCA
(A)
MFA (A)
MSC (A)
RLA (A)
KW
FLA (A)
4kW
220‐240
50
198
254
14
18
30
‐
11.3
0.094
0.9
6kW
220‐240
50
198
254
14
18
30
‐
11.3
0.094
0.9
8kW
220‐240
50
198
254
19
19
30
‐
16.7
0.195
1.7
10kW
220‐240
50
198
254
19
19
30
‐
16.7
0.195
1.7
Remove the switch box cover
Unit (kW)
4/6
8/10
Maximum overcurrent
protector(MOP)
18 A
19 A
Wiring size
4 mm
2
4 mm
2
Stated values are maximum values (see electrical data for exact values).
NOTE
MCA :
Max. Circuit Amps. (A)
TOCA :
Total Over‐current Amps. (A)
MFA :
Max. Fuse Amps. (A)
MSC :
Max. Fuse Amps. (A)
FLA :
In nominal cooling or heating test condition
,
the input Amps of compressor
where MAX. Hz can operate Rated Load Amps. (A);
KW :
Rated Motor Output
FLA :
Full Load Amps. (A)
Summary of Contents for HPS-22CH65AERI/O1 R32
Page 2: ......
Page 53: ...VIVAX HR 50 DODATAK B Dijagram ožičenja s električnim upravljanjem 4 10kW ...
Page 57: ...VIVAX HR ...
Page 58: ... HR VIVAX 1 ...
Page 89: ...VIVAX HR 32 STRUKTURA IZBORNIKA PREGLED ...
Page 90: ... HR VIVAX 33 ...
Page 145: ...VIVAX ENG 50 ANNEX B Electrically controlled wiring diagram 4 10kW ...
Page 149: ...VIVAX ENG ...
Page 150: ... ENG VIVAX 1 ...
Page 181: ...VIVAX ENG 32 MENU STRUCTURE OVERVIEW ...
Page 182: ... ENG VIVAX 33 ...
Page 187: ......
Page 205: ...3 4 3 4 3 4 ...
Page 208: ...ZZZ 9 9 FRP ...