Technical data
Technisches Handbuch
Version 5.2
24
2. Parametrise the
"TCP/IP client - Init"
object and set the
IP address
and the port of the
IOBox.
The IOBox IP address is in the as-delivered status: 192.168.0.254 and subnetwork mask:
255.255.255.0
3. Parametrise the
"TCP/IP client
– Send"
object. Select the previously set up
"TCP/IP
client - Init"
object and set the object type to
"-character string-"
under the character string
4. As a result, the command to change the IP address is entered in the following format:
CIP
<IPAddr,Mask,Gateway,DNS1,DNS2,HostName>
Example entry:
CIP<192.168.0.10,255.255.255.0,192.168.0.1,0.0.0.0,0.0.0.0,HOST_VOE>
5. Process the objects "TCP/IP client - Init" and "TCP/IP client
– Send".
The IP address of the IOBox is now changed.