Technical data
Technisches Handbuch
Version 5.2
16
OUT/ROUT Switches the outputs OUT1…4
Write:
OUTx<STATUS>
Answer: none
_OUTx<STATUS>
Answer: „ACK“
OUT1<0..1>
0 = Switches OUT1 off
with CFO1<0,xxxx> Output OUT1.24 is switched off and the PWM signal
at output OUT1.PWM is stopped.
with CFO1<1,xxxx> the PWM signal is stopped at Output OUT1.24.
1 = Switches OUT1 on
with CFO1<0,xxxx> Output OUT1.24 is switched on and the PWM signal
at Output OUT1.PWM is output.
with CFO1<1,xxxx> the PWM signal is output at Output OUT1.24.
OUT2<x>
see OUT1<x>
OUT3<x>
see OUT1<x>
OUT4<x>
see OUT1<x>
Read:
ROUT1
Answer: OUT1<0..1>
ROUT2
Answer: OUT2<0..1>
ROUT3
Answer: OUT3<0..1>
ROUT4
Answer: OUT4<0..1>
OUTP Switches the outputs OUT1...4 with PWM value
Write:
OUTPx<STATUS,PWM>
Answer: none
_OUTPx<STATUS,PWM>
Answer: „ACK“
OUTP1<0..1,0..100> 0 = Switches OUT1 off
with CFO1<0,xxxx> Output OUT1.24 is switched off and the PWM
signal at output OUT1.PWM is stopped.
with CFO1<1,xxxx> the PWM signal is stopped at Output OUT1.24.
1 = Switches OUT1 on
with CFO1<0,xxxx> Output OUT1.24 is switched on and the PWM
signal at Output OUT1.PWM is output.
with CFO1<1,xxxx> the PWM signal is output at Output OUT1.24.
OUTP1<0..1,0..100> 0..100% Brightness for OUT1.