Bit
Name
Function
0
STS_SYNC
Reset was active
1
STS_CTRL_COMP is set when
comparison bit
is enabled
2
STS_SW-GATE
Status software gate
(set when
SW gate
is active)
3
STS_RST
Status reset input
4 -
reserved
5
STS_GATE
Status internal gate
(set when internal gate active)
6 STS_COMP
Status
comparison bit
7
STS_C_DN
Status set at counter direction backward
8
STS_C_UP
Status set at counter direction forward
9
STS_CMP*
Status comparison is set when the
comparison condition is met. If comparison
is parameterized
never
, the bit is never set
10
STS_END*
Status is set when
end value
was reached
11
STS_OFLW*
Status is set at overflow
12
STS_UFLW*
Status is set at underflow
13
STS_ZP*
Status is set at zero run
14 ... 15
-
reserved
*
The bits remain set until reset with RES_SET (bit 6
control word
).
Bit
Name
Function
0
CTRL_SYNC_SET activates the reset mode
1 CTRL_COMP_SET
enables
the
comparison bit
2
SW_GATE_SET
sets the software gate
3 -
reserved
4 -
reserved
5
COUNTERVAL_SET sets counter temporarily to the value of
set
value
6
RES_SET
resets the bits STS_CMP, STS_END,
STS_OFLW, STS_UFLW and STS_ZP
with
edge 0-1
7 -
reserved
8
CTRL_SYNC_RESET deactivates the reset mode
9 CTRL_COMP_RESET disables
the
comparison bit
10
SW_GATE_RESET resets the software gate
11 ... 15
-
reserved
CSTS_I
Counter status
CCTRL_I
Control word
Summary of Contents for SLIO System FM 050-1BA10
Page 1: ...VIPA System SLIO FM 050 1BA10 Manual HB300E_FM RE_050 1BA10 Rev 10 30 July 2010...
Page 4: ...Contents Manual VIPA System SLIO ii HB300E FM RE_050 1BA10 Rev 10 30...
Page 8: ...Safety information Manual VIPA System SLIO 4 HB300E FM RE_050 1BA10 Rev 10 30...
Page 56: ...Chapter 3 Deployment Manual VIPA System SLIO 3 24 HB300E FM RE_050 1BA10 Rev 10 30...