Chapter 3 Deployment
Manual VIPA System SLIO
3-20
HB300E - FM - RE_050-1BB00 - Rev. 10/30
Effect at counter value
=
comparison value
8
7
6
5
4
3
2
1
0
Comparison value
Hysteresis
Comparison bit:
Hysteresis = 0
Hysteresis = 3
Counter value
1
2
3
4
5
6
7
(1)
Counter value
=
comparison value
→
comparison bit
is set and
hysteresis
activated
(2) Leave
hysteresis
range
→
comparison bit
is reset and
Counter value
<
comparison value
(3)
Counter value
=
comparison value
→
comparison bit
is set and
hysteresis
activated
(4)
Comparison bit
is reset for leaving
hysteresis
range and
counter value
>
comparison value
(5)
Counter value
=
comparison value
→
comparison bit
is set and
hysteresis
activated
(6)
Counter value
=
comparison value
and
hysteresis
active
→
comparison bit
remains set
(7) Leave
hysteresis
range and
counter value
≥
comparison value
→
comparison bit
is reset
With reaching the comparison condition the
hysteresis
gets active. At active
hysteresis
the comparison result remains unchanged until the
counter value
leaves the set
hysteresis
range. After leaving the
hysteresis
range a new
hysteresis
is only activated with again reaching the comparison conditions.
Summary of Contents for SLIO FM 050-1BB00
Page 1: ...VIPA System SLIO FM 050 1BB00 Manual HB300E_FM RE_050 1BB00 Rev 10 30 July 2010...
Page 4: ...Contents Manual VIPA System SLIO ii HB300E FM RE_050 1BB00 Rev 10 30...
Page 8: ...Safety information Manual VIPA System SLIO 4 HB300E FM RE_050 1BB00 Rev 10 30...
Page 56: ...Chapter 3 Deployment Manual VIPA System SLIO 3 24 HB300E FM RE_050 1BB00 Rev 10 30...